Daikin FDKS35CVMB Especificações

Consulte online ou descarregue Especificações para Aparelhos de ar condicionado "split system" Daikin FDKS35CVMB. Daikin FDKS35CVMB Specifications Manual do Utilizador

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir

Resumo do Conteúdo

Página 1 - Inverter Multi for 2 Rooms

D-Series[Applied Models]zInverter Multi : Cooling OnlyzInverter Multi : Heat Pump Inverter Multi for 2 RoomsSiBE 12 - 519

Página 2 - D-Series

SiBE12-519List of Functions 1Part 1List of Functions1. Cooling Only...

Página 3

SiBE12-519 InstructionSystem Configuration 912.6 Adjusting the Air Flow DirectionFTK(X)S20/25/35DAdjusting the Air Flow DirectionYou can adjust the ai

Página 4 - Table of Contents iii

Instruction SiBE12-51992 System ConfigurationTo start COMFORT AIRFLOW operation3. Press “COMFORT AIRFLOW button”.The flap position will change, preve

Página 5

SiBE12-519 InstructionSystem Configuration 93FTK(X)S20/25/35CAdjusting the Air Flow DirectionYou can adjust the air flow direction to increase your co

Página 6 - 1. Introduction

Instruction SiBE12-51994 System Configuration To adjust the vertical blades (louvres)Hold the knob and move the louvres.(You will find a knob on the l

Página 7

SiBE12-519 InstructionSystem Configuration 95FLK(X)S25/35Adjusting the Air Flow DirectionYou can adjust the air flow direction to increase your com-fo

Página 8 - 1.1.3 Inspection after Repair

Instruction SiBE12-51996 System Configuration To adjust the vertical blades (louvres)• When adjusting the louvre, use a robust and stable stool and w

Página 9 - 1.1.5 Using Icons List

SiBE12-519 InstructionSystem Configuration 972.7 POWERFUL OperationPOWERFUL OperationPOWERFUL operation quickly maximizes the cooling (heating) effect

Página 10 - List of Functions

Instruction SiBE12-51998 System Configuration2.8 OUTDOOR UNIT SILENT OperationOUTDOOR UNIT SILENT OperationOUTDOOR UNIT SILENT operation lowers the n

Página 11 - 1. Cooling Only

SiBE12-519 InstructionSystem Configuration 992.9 ECONO OperationECONO OperationECONO operation is a function which enables efficient operation by lowe

Página 12 - — : No Functions

Instruction SiBE12-519100 System Configuration2.10 HOME LEAVE OperationHOME LEAVE OperationHOME LEAVE operation is a function which allows you to reco

Página 13 - 2. Heat Pump

Cooling Only SiBE12-5192 List of Functions1. Cooling OnlyCategory FunctionsFTKS20-35D(2)VMW(L)(9)FTKS20-35CVMB(9)(8)Category FunctionsFTKS20-35D(2)VMW

Página 14 - List of Functions 5

SiBE12-519 InstructionSystem Configuration 101What’s the HOME LEAVE operationIs there a set temperature and air flow rate which is most comfortable,

Página 15 - 6 List of Functions

Instruction SiBE12-519102 System Configuration2.11 INTELLIGENT EYE OperationFTK(X)S20/25/35DINTELLIGENT EYE Operation“INTELLIGENT EYE” is the infrared

Página 16 - Specifications

SiBE12-519 InstructionSystem Configuration 103INTELLIGENT EYE Operation“INTELLIGENT EYE” is useful for Energy SavingNotes on “INTELLIGENT EYE”CAUTION

Página 17

Instruction SiBE12-519104 System ConfigurationFTK(X)S20/25/35CINTELLIGENT EYE Operation“INTELLIGENT EYE” is the infrared sensor which detects the huma

Página 18 - 50Hz 230V

SiBE12-519 InstructionSystem Configuration 105 To adjust the angle of the INTELLIGENT EYE sensor• You can adjust the angle of the INTELLIGENT EYE sens

Página 19

Instruction SiBE12-519106 System Configuration2.12 TIMER OperationTIMER OperationTimer functions are useful for automatically switching the air condit

Página 20 - Specifications 11

SiBE12-519 InstructionSystem Configuration 107 To use ON TIMER operation• Check that the clock is correct. If not, set the clock to the present time.

Página 21 - 1.2 Outdoor Units

Instruction SiBE12-519108 System Configuration2.13 Note for Multi SystemNote for Multi System〈〈 〈〈 〈〈 〈〈 What is a “Multi System”? 〉〉〉〉〉〉〉〉This system

Página 22 - 1.2.1 Combination Capacity

SiBE12-519 InstructionSystem Configuration 109 Priority Room SettingThe Priority Room Setting requires initial programming during installation. Please

Página 23

Instruction SiBE12-519110 System Configuration2.14 Care and CleaningFTK(X)S20/25/35DCare and CleaningCAUTION Indoor unit, Outdoor unit and Remote co

Página 24 - Specifications 15

SiBE12-519 Cooling OnlyList of Functions 3Category FunctionsFDKS25·35CVMBFLKS25·35BVMB2MKS40DVMBCategory FunctionsFDKS25·35CVMBFLKS25·35BVMB2MKS40DVMB

Página 25

SiBE12-519 InstructionSystem Configuration 1111. Open the front panel. 2. Pull out the air filters.•Push a little upwards the tab at the center of eac

Página 26 - Specifications 17

Instruction SiBE12-519112 System ConfigurationNOTECheckBefore a long idle period1. Operate the “FAN only” for several hours on a fine day to dry out t

Página 27

SiBE12-519 InstructionSystem Configuration 113FTK(X)S20/25/35CCare and CleaningCAUTION Indoor unit, Outdoor unit and Remote controller1. Wipe them w

Página 28 - 2.2.1 Combination Capacity

Instruction SiBE12-519114 System Configuration1. Open the front grille. 2. Pull out the air filters.•Push a little upwards the tab at the center of e

Página 29 - 20 Specifications

SiBE12-519 InstructionSystem Configuration 115Check Before a long idle period1. Operate the “FAN only” for several hours on a fine day to dry out the

Página 30 - Connector Wiring Diagram

Instruction SiBE12-519116 System ConfigurationFDK(X)S25/35CCARECare and CleaningCAUTION Cleaning the air filter.1.Removing the air filter.• Rear suc

Página 31 - 1.1 Wall Mounted Type

SiBE12-519 InstructionSystem Configuration 117 Cleaning the drain pan•Clean the drain pan periodically, or drain piping may be clogged with dust and m

Página 32

Instruction SiBE12-519118 System ConfigurationFLK(X)S25/35Care and CleaningCAUTION Indoor unit, Outdoor unit and Remote controller1. Wipe them with

Página 33 - 1.1.2 FTK(X)S20~35C

SiBE12-519 InstructionSystem Configuration 1191. Open the front grille.2. Pull out the air filters.• Push upwards the tab at the center of each air f

Página 34

Instruction SiBE12-519120 System ConfigurationCheck Before a long idle period1. Operate the “fan only” for several hours on a fine day to dry out the

Página 35 - PCB Detail

Heat Pump SiBE12-5194 List of Functions2. Heat PumpCategory FunctionsFTXS20-35D(2)VMW(L)(9)FTXS20-35CVMB(9)(8)Category FunctionsFTXS20-35D(2)VMW(L)(9)

Página 36 - 1.2 Duct Connected Type

SiBE12-519 InstructionSystem Configuration 1212.15 TroubleshootingTrouble ShootingThe following cases are not air conditioner troubles but have some r

Página 37

Instruction SiBE12-519122 System ConfigurationPlease check again before calling a repair person.Check again.Case CheckThe air conditioner does not ope

Página 38

SiBE12-519 InstructionSystem Configuration 123WARNING When an abnormality (such as a burning smell) occurs, stop operation and turn the breaker OFF

Página 39 - PCB(4): Signal Receiver PCB

Instruction SiBE12-519124 System ConfigurationFAULT DIAGNOSIS BY REMOTE CONTROLLERIn the ARC433A series, the temperature display sections on the main

Página 40 - 1.4 Outdoor Unit

SiBE12-519 InstructionSystem Configuration 125LED ON OUTDOOR UNIT PCB 3MXS, 3MKS, 4MXS, 4MKS seriesLED ON OUTDOOR UNIT PCB 2MXS, 2MKS series

Página 41

Instruction SiBE12-519126 System Configuration

Página 42 - Function and Control

SiBE12-519Service Diagnosis 127Part 6Service Diagnosis1. Caution for Diagnosis...

Página 43 - 1. Main Functions

Caution for Diagnosis SiBE12-519128 Service Diagnosis1. Caution for DiagnosisThe operation lamp flashes when any of the following errors is detected.1

Página 44

SiBE12-519 Caution for DiagnosisService Diagnosis 129Caution: Operation stops suddenly. (Operation lamp blinks.)Cause of above trouble could be "

Página 45 - Auto-Swing

Problem Symptoms and Measures SiBE12-519130 Service Diagnosis2. Problem Symptoms and MeasuresSymptom Check Item Details of Measure Reference Page None

Página 46 - (R2818) (R2818)

SiBE12-519 Heat PumpList of Functions 5Category FunctionsFDXS25·35CVMBFLXS25·35BVMB2MXS40DVMBCategory FunctionsFDXS25·35CVMBFLXS25·35BVMB2MXS40DVMBBas

Página 47 - 1.4 Programme Dry Function

SiBE12-519 Service Check FunctionService Diagnosis 1313. Service Check FunctionIn the ARC433A series remote controller, the temperature display sectio

Página 48 - 1.5 Automatic Operation

Service Check Function SiBE12-519132 Service DiagnosisCheck Method 2 1. Enter the diagnosis mode.Press the 3 buttons (TEMP,TEMP, MODE) simultaneousl

Página 49 - 1.6 Thermostat Control

SiBE12-519 Service Check FunctionService Diagnosis 1335. Press the TEMP button.Press TEMP or TEMP and change the digit until you hear the sound of “

Página 50 - 1.7 Night Set Mode

Troubleshooting SiBE12-519134 Service Diagnosis4. Troubleshooting4.1 Error Codes and Description: Displayed only when system-down occurs.Code Indicat

Página 51 - 1.8 ECONO Mode

SiBE12-519 TroubleshootingService Diagnosis 1354.2 Indoor Unit PCB AbnormalityRemote Controller DisplayA1Method of Malfunction DetectionEvaluation of

Página 52 - 1.9 INTELLIGENT EYE

Troubleshooting SiBE12-519136 Service Diagnosis4.3 Freeze-up Protection Control or High Pressure ControlRemote Controller DisplayA5Method of Malfuncti

Página 53 - 44 Function and Control

SiBE12-519 TroubleshootingService Diagnosis 137TroubleshootingCheck No.06Refer to P.173NONONOCheck No. 06Indoor unit heat exchanger thermistor checkCh

Página 54 - 1.10 HOME LEAVE Operation

Troubleshooting SiBE12-519138 Service Diagnosis4.4 Fan Motor or Related Abnormality4.4.1 AC MotorRemote Controller DisplayA6Method of Malfunction Dete

Página 55

SiBE12-519 TroubleshootingService Diagnosis 1394.4.2 DC MotorRemote Controller DisplayA6Method of Malfunction DetectionThe rotation speed detected by

Página 56 - 1.12 Other Functions

Troubleshooting SiBE12-519140 Service DiagnosisTroubleshootingCheck No.01Refer to P.170Replace fan motor.Replace indoor unit PCB.Replace indoor unit P

Página 57 - 1.12.10Auto-restart Function

Heat Pump SiBE12-5196 List of Functions

Página 58 - 2.1 Main Structural Parts

SiBE12-519 TroubleshootingService Diagnosis 1414.5 Thermistor or Related Abnormality (Indoor Unit)Remote Controller DisplayC4, C9 Method of Malfunctio

Página 59 - 2.2 Function of Thermistor

Troubleshooting SiBE12-519142 Service Diagnosis4.6 Freeze-up Protection ControlRemote Controller DisplayA5Method of Malfunction DetectionIndoor unit i

Página 60 - Function and Control 51

SiBE12-519 TroubleshootingService Diagnosis 143TroubleshootingCheck No.04Refer to P.171Check No.06Refer to P.173Check the wiring and piping.Check No.

Página 61 - 2.2.2 Cooling Only Model

Troubleshooting SiBE12-519144 Service Diagnosis4.7 OL Activation (Compressor Overload)Remote Controller DisplayE5Method of Malfunction DetectionA comp

Página 62 - 3. Control Specification

SiBE12-519 TroubleshootingService Diagnosis 1454.8 Compressor LockRemote Controller DisplayE6Method of Malfunction DetectionA compressor lock is detec

Página 63 - 3.2 Frequency Control

Troubleshooting SiBE12-519146 Service Diagnosis4.9 DC Fan LockRemote Controller DisplayE7Method of Malfunction DetectionA fan motor or related error i

Página 64

SiBE12-519 TroubleshootingService Diagnosis 1474.10 Input Over Current DetectionRemote Controller DisplayE8Method of Malfunction DetectionAn input ove

Página 65 - 56 Function and Control

Troubleshooting SiBE12-519148 Service DiagnosisTroubleshootingCheck No.07Refer to P.174Check No.08Refer to P.175Check No.14Refer to P.177Note: If the

Página 66 - 3.3.4 3 Minutes Stand-by

SiBE12-519 TroubleshootingService Diagnosis 1494.11 Four Way Valve AbnormalityRemote Controller DisplayEAMethod of Malfunction DetectionThe liquid pip

Página 67 - 3.5 Input Current Control

Troubleshooting SiBE12-519150 Service DiagnosisTroubleshootingCheck No.05Refer to P.172Check No.06Refer to P.173Check No.11Refer to P.176Correct.Recon

Página 68 - 3.7 Heating Peak-cut Control

SiBE12-519Specifications 7Part 2Specifications1. Cooling Only...

Página 69 - 3.8 Fan Control

SiBE12-519 TroubleshootingService Diagnosis 1514.12 Discharge Pipe Temperature ControlRemote Controller DisplayF3Method of Malfunction DetectionThe di

Página 70 - 3.10 Defrost Control

Troubleshooting SiBE12-519152 Service Diagnosis4.13 High Pressure Control in CoolingRemote Controller DisplayF6Method of Malfunction DetectionHigh-pre

Página 71 - 62 Function and Control

SiBE12-519 TroubleshootingService Diagnosis 153TroubleshootingCheck No.04Refer to P.171Check No.06Refer to P.173Check No.07Refer to P.174Check No.09Re

Página 72 - Function and Control 63

Troubleshooting SiBE12-519154 Service Diagnosis4.14 Position Sensor AbnormalityRemote Controller DisplayH6Method of Malfunction DetectionA compressor

Página 73 - 64 Function and Control

SiBE12-519 TroubleshootingService Diagnosis 1554.15 CT or Related AbnormalityRemote Controller DisplayH8Method of Malfunction DetectionA CT or related

Página 74 - 3.11.10 Oil Recovery Function

Troubleshooting SiBE12-519156 Service DiagnosisTroubleshootingCheck No.12Refer to P.176Note: If the model doesn't have SPM, replace the outdoor u

Página 75 - 3.12 Malfunctions

SiBE12-519 TroubleshootingService Diagnosis 1574.16 Thermistor or Related Abnormality (Outdoor Unit)Remote Controller DisplayP4,J3,J6,J8,J9,H9Method o

Página 76 - 3.13 Forced Operation Mode

Troubleshooting SiBE12-519158 Service DiagnosisTroubleshootingCheck No.06Refer to P.173P4 : Radiation fin thermistorJ3 : Discharge pipe thermistorJ6 :

Página 77 - 3.14 Additional Function

SiBE12-519 TroubleshootingService Diagnosis 1594.17 Electrical Box Temperature RiseRemote Controller DisplayL3Method of Malfunction DetectionAn electr

Página 78 - System Configuration

Troubleshooting SiBE12-519160 Service DiagnosisTroubleshootingCheck No.06Refer to P.173Check No.07Refer to P.174Check No.09Refer to P.175Turn off the

Página 79 - 1. System Configuration

Cooling Only SiBE12-5198 Specifications1. Cooling Only1.1 Indoor UnitsWall Mounted Type50Hz 230VModel FTKS20D(2)VMW(9) FTKS20D(2)VMLRated Capacity 2.0

Página 80 - 2. Instruction

SiBE12-519 TroubleshootingService Diagnosis 1614.18 Radiation Fin Temperature RiseRemote Controller DisplayL4Method of Malfunction DetectionA radiatio

Página 81 - Safety precautions

Troubleshooting SiBE12-519162 Service DiagnosisTroubleshootingCheck No.06Refer to P.173Check No.07Refer to P.174Check No.09Refer to P.175Turn off the

Página 82 - System relocation

SiBE12-519 TroubleshootingService Diagnosis 1634.19 Output Over Current DetectionRemote Controller DisplayL5Method of Malfunction DetectionAn output o

Página 83 - Names of parts

Troubleshooting SiBE12-519164 Service DiagnosisTroubleshootingCheck No.07Refer to P.174Check No.08Refer to P.175Check No.13Refer to P.177Note: If the

Página 84 - Outdoor Unit

SiBE12-519 TroubleshootingService Diagnosis 1654.20 Insufficient GasRemote Controller DisplayU0Method of Malfunction DetectionGas shortage detection I

Página 85 - Remote Controller

Troubleshooting SiBE12-519166 Service DiagnosisTroubleshootingCheck No.04Refer to P.171Check No.06Refer to P.173Reconnect in position.Open the stop va

Página 86

SiBE12-519 TroubleshootingService Diagnosis 1674.21 Over-voltage DetectionRemote Controller DisplayU2Method of Malfunction DetectionAn abnormal voltag

Página 87

Troubleshooting SiBE12-519168 Service Diagnosis4.22 Anti-icing Function in Other Rooms / Unspecified Voltage (between Indoor and Outdoor Units)Remote

Página 88

SiBE12-519 TroubleshootingService Diagnosis 1694.23 Outdoor Unit PCB Abnormality or Signal Transmission Circuit AbnormalityRemote Controller DisplayU4

Página 89

Check SiBE12-519170 Service Diagnosis5. Check5.1 How to Check5.1.1 Fan Motor Connector Output CheckCheck No.01 1. Check connector connection.2. Check

Página 90 - ■ Outdoor Unit

SiBE12-519 Cooling OnlySpecifications 950Hz 230VModel FTKS35D(2)VMW(9) FTKS35D(2)VMLRated Capacity 3.5kW Class 3.5kW ClassFront Panel Color White Silv

Página 91 - ■ Remote Controller

SiBE12-519 CheckService Diagnosis 1715.1.2 Electronic Expansion Valve CheckCheck No.04 Conduct the followings to check the electronic expansion valve

Página 92

Check SiBE12-519172 Service Diagnosis5.1.3 Four Way Valve Performance CheckCheck No.05Turn off the power and turn it on again.Start the heating-mode r

Página 93

SiBE12-519 CheckService Diagnosis 1735.1.4 Thermistor Resistance CheckCheck No.06 Remove the connectors of the thermistors on the PCB, and measure the

Página 94

Check SiBE12-519174 Service Diagnosis5.1.5 Installation Condition CheckCheck No.07Installation condition checkNormalChange the position of the air dis

Página 95 - Preparation Before Operation

SiBE12-519 CheckService Diagnosis 1755.1.6 Discharge Pressure CheckCheck No.085.1.7 Outdoor Unit Fan System Check (With DC Motor)Check No.09Discharge

Página 96

Check SiBE12-519176 Service Diagnosis5.1.8 Inverter Units Refrigerant System CheckCheck No.115.1.9 Capacitor Voltage CheckCheck No.12 Before this chec

Página 97 - Turn the breaker ON

SiBE12-519 CheckService Diagnosis 1775.1.10 Power Transistor CheckCheck No.13Checking the power transistorzNever touch any live parts for at least 10

Página 98 - 2. Press “ON/OFF button”

Check SiBE12-519178 Service Diagnosis5.1.12 Turning Speed Pulse Input on the Outdoor Unit PCB CheckCheck No.15 <Propeller fan motor>Make sure th

Página 99 - 90 System Configuration

SiBE12-519Removal Procedure 179Part 7 Removal Procedure1. Outdoor Unit...

Página 100 - 1. Press “SWING button”

Outdoor Unit SiBE12-519180 Removal Procedure1. Outdoor Unit1.1 Removal of the Panels / Fan MotorProcedure Warning Be sure to wait 10 minutes or more a

Página 101 - 〈HEAT〉 The flap will go down

Cooling Only SiBE12-51910 Specifications50Hz 230VDuct Connected Type50Hz 230VNote:1. The operating sound is based on the rear side suction inlet and t

Página 102 - To adjust the horizontal

SiBE12-519 Outdoor UnitRemoval Procedure 181Make sure that the seven claws are fit securely when reassembling.2. Remove the top panel.1Loosen the fou

Página 103 - (louvres)

Outdoor Unit SiBE12-519182 Removal Procedure3Undo the claws and pull the front panel out towards you.The front panel has four claws.It is possible t

Página 104

SiBE12-519 Outdoor UnitRemoval Procedure 1833Pull the fan motor lead wire away.4Release the four claws and remove the electrical box cover.5Unscrew th

Página 105

Outdoor Unit SiBE12-519184 Removal ProcedureStepProcedure Points6Remove the propeller fan.Align mark of the propeller fan with D-cut section of the m

Página 106 - POWERFUL Operation

SiBE12-519 Outdoor UnitRemoval Procedure 1851.2 Removal of the PCBProcedure Warning Be sure to wait 10 minutes or more after turning off all power sup

Página 107 - 1. Press “SILENT button”

Outdoor Unit SiBE12-519186 Removal Procedure4Disconnect the relaying connector for the compressor.5Disconnect the two connectors of the reactor.6Disco

Página 108 - ECONO Operation

SiBE12-519 Outdoor UnitRemoval Procedure 1878Disconnect the harnesses.9Loosen the screw of the terminal strip board.A thermal fuse is united with the

Página 109 - HOME LEAVE Operation

Outdoor Unit SiBE12-519188 Removal Procedure11Lift the PCB from the heat exchanger side, and release from the two claws.Mind that not to break the PC

Página 110 - Useful in these cases

SiBE12-519 Outdoor UnitRemoval Procedure 189StepProcedure Points14The illustration shows the layout of the PCB (parts side).15Loosen the two screws of

Página 111 - INTELLIGENT EYE Operation

Outdoor Unit SiBE12-519190 Removal Procedure1.3 Removal of the Electrical BoxProcedure Warning Be sure to wait 10 minutes or more after turning off al

Página 112

SiBE12-519Table of Contents iInverter Multi for 2 RoomsD-SerieszCooling OnlyOutdoor Unit Indoor Unit2MKS40DVMB FTKS20D(2)VMW(L)(9) FDKS25CVMBFTKS25D(2

Página 113

SiBE12-519 Cooling OnlySpecifications 11Floor / Ceiling Suspended Dual Type50Hz 230VModel FLKS25BVMB FLKS35BVMBRated Capacity 2.5kW Class 3.5kW ClassF

Página 114 - Notes on “INTELLIGENT EYE”

SiBE12-519 Outdoor UnitRemoval Procedure 1914Disconnect all the connectors.As for the connectors, refer to the removal procedure of PCB.5Disconnect t

Página 115 - TIMER Operation

Outdoor Unit SiBE12-519192 Removal Procedure7Lift the electrical box up.8Release the wire clamp from the back side of the electrical box.9Remove the e

Página 116 - ATTENTION

SiBE12-519 Outdoor UnitRemoval Procedure 1931.4 Removal of the Sound BlanketProcedure Warning Be sure to wait 10 minutes or more after turning off all

Página 117 - Note for Multi System

Outdoor Unit SiBE12-519194 Removal Procedure3The partition plate is fixed to the bottom frame with a claw.Lift it and pull out towards you.Fit the cl

Página 118 - Priority Room Setting

SiBE12-519 Outdoor UnitRemoval Procedure 195StepProcedure Points7Remove the sound blanket (side-inner A).8Remove the sound blanket (side-inner B).9Rem

Página 119 - Care and Cleaning

Outdoor Unit SiBE12-519196 Removal Procedure1.5 Removal of the ThermistorProcedure Warning Be sure to wait 10 minutes or more after turning off all po

Página 120 - [ Replacement]

SiBE12-519 Outdoor UnitRemoval Procedure 1971.6 Removal of the Four Way ValveProcedure Warning Be sure to wait 10 minutes or more after turning off al

Página 121 - Before a long idle period

Outdoor Unit SiBE12-519198 Removal ProcedureStepProcedure PointsWarningVentilate when refrigerant leaks during the work.(If refrigerant contacts fire,

Página 122

SiBE12-519 Outdoor UnitRemoval Procedure 1991.7 Removal of the Electronic Expansion ValveProcedure Warning Be sure to wait 10 minutes or more after tu

Página 123

Outdoor Unit SiBE12-519200 Removal Procedure1.8 Removal of the CompressorProcedure Warning Be sure to wait 10 minutes or more after turning off all po

Página 124

Cooling Only SiBE12-51912 Specifications1.2 Outdoor Units50Hz 230VNote:1.See “Combination Capacity”.2. The data are based on the conditions shows in

Página 125

SiBE12-519 Outdoor UnitRemoval Procedure 201StepProcedure PointsBefore working, make sure that the refrigerant is empty in the circuit.Be sure to ap

Página 126 - Cleaning the drain pan

Outdoor Unit SiBE12-519202 Removal Procedure

Página 127

SiBE12-519Others 203Part 8Others1. Others ...2041.1 Test

Página 128

Others SiBE12-519204 Others1. Others1.1 Test Run from the Remote ControllerFor Heat pump In cooling mode, select the lowest programmable temperature;

Página 129 - ■ Before a long idle period

SiBE12-519 OthersOthers 2051.2 Jumper Settings1.2.1 When Two Units are Installed in One RoomWhen two indoor units are installed in one room, the two w

Página 130 - Trouble Shooting

Others SiBE12-519206 Others1.2.3 Adjusting the Angle of the Intelligent Eye SensorFTK(X)S20-35COnce installation of the indoor unit is complete, adju

Página 131 - Case Check

SiBE12-519Appendix 207Part 9Appendix1. Piping Diagrams...2081.1 Indoor

Página 132 - Disposal requirements

Piping Diagrams SiBE12-519208 Appendix1. Piping Diagrams1.1 Indoor Units1.1.1 Wall Mounted TypeFTKS20D(2)VMW(L)(9), FTKS25D(2)VMW(L)(9) FTKS35D(2)VMW(

Página 133 - Fault diagnosis

SiBE12-519 Piping DiagramsAppendix 2091.1.2 Duct Connected Type1.1.3 Floor / Ceiling Suspended Dual TypeFDK(X)S25CVMB, FDK(X)S35CVMBFIELD PIPINGFIELD

Página 134 - System Configuration 125

Piping Diagrams SiBE12-519210 Appendix1.2 Outdoor Units2MKS40DVMB2MXS40DVMBREFRIGERANT FLOWHEAT EXCHANGERTHERMISTOR (DE)BRANCHPIPEOUTDOOR UNITCOOLING7

Página 135 - 126 System Configuration

SiBE12-519 Cooling OnlySpecifications 131.2.1 Combination CapacityWall Mounted Type D SeriesCooling [230V]50HzNote:1. Cooling capacity is based on 27°

Página 136 - Service Diagnosis

SiBE12-519 Wiring DiagramsAppendix 2112. Wiring Diagrams2.1 Indoor Units2.1.1 Wall Mounted TypeFTKS20D(2)VMW(L)(9), FTKS25D(2)VMW(L)(9), FTKS35D(2)VMW

Página 137 - 1. Caution for Diagnosis

Wiring Diagrams SiBE12-519212 Appendix2.1.2 Duct Connected TypeFDK(X)S25CVMB, FDK(X)S35CVMB 2.1.3 Floor / Ceiling Suspended Dual TypeFLK(X)S25BVMB, FL

Página 138 - Service Diagnosis 129

SiBE12-519 Wiring DiagramsAppendix 2132.2 Outdoor Units2MKS40DVMB2MXS40DVMB3D039654BPCB1 PCB2S301RED1REDZ1CWYLWVYLW3UVTRM1BLUBLU5M1CU-N+WBRNBRN(FIN)S9

Página 139

Wiring Diagrams SiBE12-519214 Appendix

Página 140 - 3. Service Check Function

SiBE12-519Index i IndexNumerics3 minutes stand-by ...57AA1 ...

Página 141 - 132 Service Diagnosis

SiBE12-519ii IndexFF3 ...151F6 ...

Página 142 - Service Diagnosis 133

SiBE12-519Index iiioutdoor unit PCB abnormality ...169OUTDOOR UNIT SILENT operation ...98output over cur

Página 143 - 4. Troubleshooting

SiBE12-519iv IndexU2 ...167U4 ...

Página 144

SiBE12-519Drawings & Flow Charts vDrawings & Flow ChartsAanti-icing function in other rooms ...168ARC433A ...

Página 145 - 136 Service Diagnosis

SiBE12-519vi Drawings & Flow ChartsFTXS25CVMB(9)(8) ...208FTXS25D(2)VMW(L)(9) ...

Página 146 - Refer to P.173

Heat Pump SiBE12-51914 Specifications2. Heat Pump2.1 Indoor UnitsWall Mounted Type50Hz 230VModelFTXS20D(2)VMW(9) FTXS20D(2)VMLCooling Heating Cooling

Página 147 - 4.4.1 AC Motor

The specifications, designs, and information in this brochure are subject to change without notice. All rights reservedcDealerHead Office:Umeda Ce

Página 148 - 4.4.2 DC Motor

SiBE12-519 Heat PumpSpecifications 1550Hz 230VModelFTXS35D(2)VMW(9) FTXS35D(2)VMLCooling Heating Cooling HeatingRated Capacity 3.5kW Class 3.5kW Class

Página 149 - Refer to P.170

Heat Pump SiBE12-51916 Specifications50Hz 230VDuct Connected Type50Hz 230VNote:1. The operating sound is based on the rear side suction inlet and the

Página 150 - Service Diagnosis 141

SiBE12-519 Heat PumpSpecifications 17Floor / Ceiling Suspended Dual Type50Hz 230VModelFLXS25BVMB FLXS35BVMBCooling Heating Cooling HeatingRated Capaci

Página 151 - 142 Service Diagnosis

Heat Pump SiBE12-51918 Specifications2.2 Outdoor UnitsNote:1. See “Combination Capacity”.2. The data are based on the conditions shows in the table b

Página 152 - Refer to P.171

SiBE12-519 Heat PumpSpecifications 192.2.1 Combination CapacityWall Mounted Type D Series Cooling [230V]50HzHeating [230V]50HzNote:1. Cooling capacity

Página 153 - 144 Service Diagnosis

Heat Pump SiBE12-51920 Specifications

Página 154 - 4.8 Compressor Lock

SiBE12-519ii Table of Contents1. Introduction ...v1.1 Safety

Página 155 - 4.9 DC Fan Lock

SiBE12-519Printed Circuit Board Connector Wiring Diagram 21Part 3Printed Circuit BoardConnector Wiring Diagram1. Printed Circuit Board Connector Wirin

Página 156 - Service Diagnosis 147

Printed Circuit Board Connector Wiring Diagram SiBE12-51922 Printed Circuit Board Connector Wiring Diagram1. Printed Circuit Board Connector Wiring Di

Página 157 - 148 Service Diagnosis

SiBE12-519 Printed Circuit Board Connector Wiring DiagramPrinted Circuit Board Connector Wiring Diagram 23PCB Detail PCB(1): Control PCBPCB(4): INTELL

Página 158 - Service Diagnosis 149

Printed Circuit Board Connector Wiring Diagram SiBE12-51924 Printed Circuit Board Connector Wiring Diagram1.1.2 FTK(X)S20~35CConnectorsNote: Other des

Página 159 - 150 Service Diagnosis

SiBE12-519 Printed Circuit Board Connector Wiring DiagramPrinted Circuit Board Connector Wiring Diagram 25PCBJP21JBJAJC5VGND12V(R2413)SW7PCB(1) Contro

Página 160 - Service Diagnosis 151

Printed Circuit Board Connector Wiring Diagram SiBE12-51926 Printed Circuit Board Connector Wiring DiagramPCB Detail

Página 161 - 152 Service Diagnosis

SiBE12-519 Printed Circuit Board Connector Wiring DiagramPrinted Circuit Board Connector Wiring Diagram 271.2 Duct Connected TypeConnectorsNote: Other

Página 162 - Service Diagnosis 153

Printed Circuit Board Connector Wiring Diagram SiBE12-51928 Printed Circuit Board Connector Wiring DiagramPCB Detail PCB(2): Display PCB

Página 163 - 154 Service Diagnosis

SiBE12-519 Printed Circuit Board Connector Wiring DiagramPrinted Circuit Board Connector Wiring Diagram 291.3 Floor / Ceiling Suspended Dual TypeConne

Página 164 - Service Diagnosis 155

Printed Circuit Board Connector Wiring Diagram SiBE12-51930 Printed Circuit Board Connector Wiring DiagramPCB Detail PCB(2): Power Supply PCBPCB(3): D

Página 165 - Refer to P.176

SiBE12-519Table of Contents iii3.10 Defrost Control ...613.11 Elec

Página 166 - P4,J3,J6,J8,J9,H9

SiBE12-519 Printed Circuit Board Connector Wiring DiagramPrinted Circuit Board Connector Wiring Diagram 311.4 Outdoor UnitConnectorsNote: Other Design

Página 167 - 158 Service Diagnosis

Printed Circuit Board Connector Wiring Diagram SiBE12-51932 Printed Circuit Board Connector Wiring DiagramPCB Detail PCB(2): Control PCB

Página 168 - Service Diagnosis 159

SiBE12-519Function and Control 33Part 4 Function and Control1. Main Functions...

Página 169 - 160 Service Diagnosis

Main Functions SiBE12-51934 Function and Control1. Main FunctionsNote: See the list of functions for the functions applicable to different models.1.1

Página 170 - Service Diagnosis 161

SiBE12-519 Main FunctionsFunction and Control 35Inverter Features The inverter provides the following features:The regulating capacity can be changed

Página 171 - 162 Service Diagnosis

Main Functions SiBE12-51936 Function and Control1.2 Power-Airflow Dual Flaps, Wide Angle Louvers and Auto-SwingPower-airflow Dual FlapsThe large flaps

Página 172 - Service Diagnosis 163

SiBE12-519 Main FunctionsFunction and Control 371.3 Fan Speed Control for Indoor UnitsControl Mode The airflow rate can be automatically controlled de

Página 173 - 164 Service Diagnosis

Main Functions SiBE12-51938 Function and Control1.4 Programme Dry FunctionProgramme dry function removes humidity while preventing the room temperatur

Página 174 - 4.20 Insufficient Gas

SiBE12-519 Main FunctionsFunction and Control 391.5 Automatic OperationAutomatic Cooling / Heating Function (Heat Pump Only)When the AUTO mode is sele

Página 175

Main Functions SiBE12-51940 Function and Control1.6 Thermostat ControlThermostat control is based on the difference between the room temperature and t

Página 176 - 4.21 Over-voltage Detection

SiBE12-519iv Table of Contents4.21 Over-voltage Detection...1674.22 Anti-icing F

Página 177 - 168 Service Diagnosis

SiBE12-519 Main FunctionsFunction and Control 411.7 Night Set ModeWhen the OFF timer is set, the Night Set circuit automatically activates.The Night S

Página 178 - Circuit Abnormality

Main Functions SiBE12-51942 Function and Control1.8 ECONO ModeOutline FTK(X)S20-35DThe "ECONO mode" reduces the maximum operating current an

Página 179 - 5. Check

SiBE12-519 Main FunctionsFunction and Control 431.9 INTELLIGENT EYEThis is the function that detects existence of humans in the room by a human motion

Página 180

Main Functions SiBE12-51944 Function and ControlSince the set temperature is shifted by 2°C higher for 40 minutes, compressor speed becomes low and c

Página 181 - Check No.05

SiBE12-519 Main FunctionsFunction and Control 451.10 HOME LEAVE OperationOutline In order to respond to the customer's need for immediate heating

Página 182

Main Functions SiBE12-51946 Function and Control1.11 Inverter POWERFUL OperationOutline In order to exploit the cooling and heating capacity to full e

Página 183 - Check No.07

SiBE12-519 Main FunctionsFunction and Control 471.12 Other Functions1.12.1 Hot Start FunctionHeat Pump OnlyIn order to prevent the cold air blast that

Página 184 - Check No.09

Main Functions SiBE12-51948 Function and Control1.12.7 Air Purifying Filter with Photocatalytic Deodorizing FunctionThis filter incorporates the benef

Página 185 - 5.1.9 Capacitor Voltage Check

SiBE12-519 Function of Main Structural PartsFunction and Control 492. Function of Main Structural Parts2.1 Main Structural PartsHeat Pump ModelCooling

Página 186 - 5.1.10 Power Transistor Check

Function of Main Structural Parts SiBE12-51950 Function and Control2.2 Function of Thermistor2.2.1 Heat Pump ModelA Outdoor Heat Exchanger Thermisto

Página 187 - 5.1.13 Hall IC Check

SiBE12-519 Introductionv1. Introduction1.1 Safety CautionsCautions and WarningsBe sure to read the following safety cautions before conducting repair

Página 188 - Removal Procedure

SiBE12-519 Function of Main Structural PartsFunction and Control 51D Indoor Heat Exchanger Thermistor (DCN)1. The indoor heat exchanger thermistors

Página 189 - 1. Outdoor Unit

Function of Main Structural Parts SiBE12-51952 Function and Control2.2.2 Cooling Only ModelA Outdoor Heat Exchanger Thermistor (DCB)1. The outdoor h

Página 190 - Procedure Points

SiBE12-519 Control SpecificationFunction and Control 533. Control Specification3.1 Mode HierarchyOutline There are two modes; the mode selected in use

Página 191

Control Specification SiBE12-51954 Function and Control3.2 Frequency ControlOutline Frequency that corresponds to each room’s capacity will be determi

Página 192

SiBE12-519 Control SpecificationFunction and Control 55For Cooling Only Model1. Determine command frequencyCommand frequency will be determined in th

Página 193 - Lead wire Propeller fan

Control Specification SiBE12-51956 Function and Control3. Limit of frequency variation widthWhen the difference between input current and input curren

Página 194 - 1.2 Removal of the PCB

SiBE12-519 Control SpecificationFunction and Control 573.3 Controls at Mode Changing / Start-up3.3.1 Preheating OperationOutline Operate the inverter

Página 195

Control Specification SiBE12-51958 Function and Control3.4 Discharge Pipe ControlOutline The discharge pipe temperature is used as the compressor&apos

Página 196

SiBE12-519 Control SpecificationFunction and Control 593.6 Freeze-up Protection ControlOutline During cooling operation, the signals being sent from t

Página 197

Control Specification SiBE12-51960 Function and Control3.8 Fan ControlOutline Fan control is carried out with following functions.1. Fan ON control fo

Página 198

Introduction SiBE12-519vi1.1.2 Cautions Regarding Products after RepairDo not repair the electrical components with wet hands.Working on the equipment

Página 199

SiBE12-519 Control SpecificationFunction and Control 613.10 Defrost ControlOutline Heat Pump OnlyDefrosting is carried out by the cooling cycle (rever

Página 200

Control Specification SiBE12-51962 Function and Control3.11 Electronic Expansion Valve Control Outline The following items are included in the electro

Página 201

SiBE12-519 Control SpecificationFunction and Control 63Detail The followings are the examples of control which function in each mode by the electronic

Página 202 - Removal Procedure 193

Control Specification SiBE12-51964 Function and Control3.11.1 Fully Closing with Power OnInitialize the electronic expansion valve when turning on the

Página 203

SiBE12-519 Control SpecificationFunction and Control 65Detail Detect DisconnectionIf a 780-second timer for open control becomes over, the following a

Página 204

Control Specification SiBE12-51966 Function and Control3.12 Malfunctions3.12.1 Sensor Malfunction DetectionSensor malfunction may occur either in the

Página 205 - 1.5 Removal of the Thermistor

SiBE12-519 Control SpecificationFunction and Control 673.12.4 Preventing Indoor FreezingDuring cooling, if the heat exchanger temperature in the opera

Página 206

Control Specification SiBE12-51968 Function and Control3.14 Additional Function3.14.1 POWERFUL Operation ModeCompressor operating frequency and outdoo

Página 207 - 198 Removal Procedure

SiBE12-519System Configuration 69Part 5System Configuration1. System Configuration...

Página 208

System Configuration SiBE12-51970 System Configuration1. System ConfigurationAfter the installation and test operation of the room air conditioner hav

Página 209 - 1.8 Removal of the Compressor

SiBE12-519 Introductionvii1.1.3 Inspection after RepairBe sure to use an exclusive power circuit for the equipment, and follow the technical standards

Página 210

SiBE12-519 InstructionSystem Configuration 712. Instruction2.1 Manual Contents and Reference Page : Illustrations are for wall mounted type FTXS20/25

Página 211 - 202 Removal Procedure

Instruction SiBE12-51972 System Configuration2.2 Safety PrecautionsSafety precautions22222222222222222Keep this manual where the operator can easily f

Página 212 - Others 203

SiBE12-519 InstructionSystem Configuration 73222222222222222222Do not stand or sit on the outdoor unit. Do not place any object on the unit to avoid i

Página 213 - 1. Others

Instruction SiBE12-51974 System Configuration2.3 Names of PartsFTK(X)S20/25/35DNames of partsIndoor UnitON/OFF16 141315121345791011862

Página 214 - 1.2 Jumper Settings

SiBE12-519 InstructionSystem Configuration 75Outdoor UnitIndoor Unit1. Air filter2. Titanium Apatite Photocatalytic Air-Purifying Filter:•These filt

Página 215 - 206 Others

Instruction SiBE12-51976 System ConfigurationRemote Controller1. Signal transmitter:• It sends signals to the indoor unit.2. Display:• It displays th

Página 216 - Appendix

SiBE12-519 InstructionSystem Configuration 77FTK(X)S20/25/35CNames of parts Indoor UnitONOFF13456791011214 15 16812 13

Página 217 - 1. Piping Diagrams

Instruction SiBE12-51978 System Configuration Outdoor Unit Indoor Unit1. Air filter2. Air purifying filter with photocatalyticdeodorizing function

Página 218 - 1.1.2 Duct Connected Type

SiBE12-519 InstructionSystem Configuration 79 Remote Controller1. Signal transmitter:•It sends signals to the indoor unit.2. Display:• It displays the

Página 219

Instruction SiBE12-51980 System ConfigurationFDK(X)S25/35C Names of partsIndoor Unit36891071452

Página 220 - 2. Wiring Diagrams

Introduction SiBE12-519viii1.1.4 Using IconsIcons are used to attract the attention of the reader to specific information. The meaning of each icon is

Página 221 - 2.1.2 Duct Connected Type

SiBE12-519 InstructionSystem Configuration 81 Outdoor Unit Indoor Unit1.Air outlet2. Air outlet grille (Field supply)• Appearance of the Air outle

Página 222 - 2.2 Outdoor Units

Instruction SiBE12-51982 System Configuration Remote Controller1. Signal transmitter:• It sends signals to the indoor unit.2. Display:• It displays t

Página 223 - 214 Appendix

SiBE12-519 InstructionSystem Configuration 83FLK(X)S25/35Names of parts Indoor UnitThe indoor unit can be installed either to the ceiling or to a wall

Página 224 - Numerics

Instruction SiBE12-51984 System Configuration Outdoor Unit Indoor Unit1. Louvres (vertical blades):The louvres are inside of the air outlet.2. Air

Página 225

SiBE12-519 InstructionSystem Configuration 85 Remote Controller1. Signal Transmitter:• It sends signals to the indoor unit.2. Display:• It displays t

Página 226 - Index iii

Instruction SiBE12-51986 System Configuration2.4 Preparation before OperationPreparation Before Operation To set the batteries1. Press with a finger

Página 227

SiBE12-519 InstructionSystem Configuration 87Preparation Before Operation To operate the remote controller• To use the remote controller, aim the tran

Página 228 - Drawings & Flow Charts

Instruction SiBE12-51988 System ConfigurationTo set the clock1. Press “CLOCK button”.is displayed.blinks.2. Press “TIMER setting button” to set the

Página 229

SiBE12-519 InstructionSystem Configuration 892.5 AUTO · DRY · COOL · HEAT · FAN OperationAUTO · DRY · COOL · HEAT · FAN OperationThe air conditioner o

Página 230 - Cautions on product corrosion

Instruction SiBE12-51990 System Configuration To change the air flow rate setting5. Press “FAN setting button”.• Indoor unit quiet operationWhen the a

Comentários a estes Manuais

Sem comentários