Setting the address of wireless remote controller
(See figure 3)
Setting from the remote controller
1
Hold down the
button and the
button for
at least 4 seconds to get the Field Set mode.
(Indicated in the display area in the figure.)
2
Press the
button and select a multiple setting
(
a
/
b
). Each time the button is pressed the display
switches between “
a
and “
b
”.
3
Press the
button and
button to set the address.
Address can be set from 1 to 6, but set it to 1~3 and
to same address as the receiver. (The receiver does
not work with address 4~6.)
4
Press the button to enter the setting.
5
Hold down the
button for at least 1 second
to quit the Field Set mode and return to normal
display.
Multiple setting
a
/
b
When the indoor unit is being operated by outside control
(central remote controller, etc.), it sometimes does not
respond to ON/OFF and temperature setting commands
from this remote controller. Check what setting the
customer wants and make the multiple setting as shown
below.
Stick the unit number label
Stick the unit number label on the air outlet of the
decoration panel and on the back of the wireless remote
controller.
Receiver installation
1
Refer to figure 5. Pass the harness from the receiver
through the wiring hole of the decoration panel. Then,
attach the receiver to the decoration panel.
2
Refer to figure 6. Hook the harness from the receiver
of the decoration panel. Be sure to push the harness
to the groove.
3
Attach the decoration panel to the indoor unit.
(Refer to the installation manual attached to the
decoration panel.)
4
Refer to figure 8. Connect the harness from the
receiver to the connector X1A on the transmitter
board.
After connecting, use the clamp to fix the two
harnesses to the transmitter board box.
5
Refer to figure 7. Use two tapping screws to attach
the transmitter board to the indoor unit, as shown in
the figure.
A
Mode
B
Address (is factory set to “
1
”)
C
Multiple setting
Remote controller
Movement when the
operation is controlled by
the other air conditioners
and equipment
Multiple
setting
Remote
controller
display
a
: Standard
All items
displayed.
When operation
changeover, temperature
setting or the like is
carried out from the
remote controller, the
indoor unit rejects the
instruction.
(Signal receiving sound
“peeh” or “pick-pick-pick”)
As a result, a discrepancy
between the operation
state of the indoor unit and
the indication of the remote
controller display occurs.
b
: Multi
System
Operations
remain
displayed
shortly after
execution.
Since the indication of the
remote controller is turned
off, no discrepancy such
as mentioned above
occurs.
NOTE
Set the Unit No. of the receiver and the