Daikin CDKS50CVMB Manual de Serviço

Consulte online ou descarregue Manual de Serviço para Aparelhos de ar condicionado "split system" Daikin CDKS50CVMB. Daikin CDKS50CVMB Service manual Manual do Utilizador

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir

Resumo do Conteúdo

Página 1 - Ser vice

Inverter Multi for 2 RoomsB-Series / D-Series[Applied Models]lInverter Multi : Cooling OnlylInverter Multi : Heat Pump SiENBE12-627Ser viceManual

Página 2 - D-Series

SiENBE12-627Printed Circuit Board Connector Wiring Diagram 1Part 1List of Functions1. Cooling Only...

Página 3

SiENBE12-627 InstructionSystem Configuration 91"Outdoor Unit"Indoor Unit"Outdoor UnitAppearance of the outdoor unit may differ from som

Página 4 - Table of Contents iii

Instruction SiENBE12-62792 System Configuration"Remote controlTEMP ON/OFF PO WERFUL MODE FA N SWING SILENT SENSOR ECONO COMFOR T TIMER ON CANCEL

Página 5

SiENBE12-627 InstructionSystem Configuration 93FTK(X)S 20/25/35 C, ATK(X)S 20/25/35 D"Indoor UnitONOFF

Página 6 - 1. Introduction

Instruction SiENBE12-62794 System Configuration"Outdoor Unit"Indoor Unit"Outdoor UnitAppearance of the outdoor unit may differ from som

Página 7

SiENBE12-627 InstructionSystem Configuration 95"Remote control1. Signal transmitter:• It sends signals to the indoor unit.2. Display:• It display

Página 8 - 1.1.3 Inspection after Repair

Instruction SiENBE12-62796 System ConfigurationFTXG 25/35 E, ATXG 25/35 E"Indoor Unit15 14 18 12 13 17 1 3 4 6 2 11 16 5 7 8 9 10 (With the pan

Página 9 - 1.1.5 Using Icons List

SiENBE12-627 InstructionSystem Configuration 97"Outdoor Unit"Indoor Unit"Outdoor UnitAppearance of the outdoor unit may differ from som

Página 10 - List of Functions

Instruction SiENBE12-62798 System Configuration"Remote control1. Signal transmitter:• It sends signals to the indoor unit.2. Display:• It display

Página 11 - 1. Cooling Only

SiENBE12-627 InstructionSystem Configuration 99FDK(X)S 25/35 C, FDK(X)S 25/35 E"Indoor Unit36891071452

Página 12 - List of Functions 3

Instruction SiENBE12-627100 System Configuration"Outdoor Unit"Indoor Unit"Outdoor UnitAppearance of the outdoor unit may differ from so

Página 13 - 4 List of Functions

Cooling Only SiENBE12-6272 List of Functions1. Cooling OnlyCategory FunctionsFTKS20-35D3VMW(L)FTKS20-35CAVMBCategory FunctionsFTKS20-35D3VMW(L)FTKS20-

Página 14 - List of Functions 5

SiENBE12-627 InstructionSystem Configuration 101"Remote Control1. Signal transmitter:• It sends signals to the indoor unit.2. Display:• It displa

Página 15 - 6 List of Functions

Instruction SiENBE12-627102 System ConfigurationFLK(X)S 25/35 B"Indoor UnitThe indoor unit can be installed either to the ceiling or to a wall. T

Página 16 - 2. Heat Pump

SiENBE12-627 InstructionSystem Configuration 103"Indoor Unit"Indoor Unit"Outdoor UnitAppearance of the outdoor unit may differ from som

Página 17 - 8 List of Functions

Instruction SiENBE12-627104 System Configuration"Remote ControlC ONTEMP ON/OFF PO WERFUL HOME LE AV E MODE TIME R FA N SWING SILENT ON CANCE L

Página 18 - List of Functions 9

SiENBE12-627 InstructionSystem Configuration 1052.4Preparation Before OperationATTENTION"To set the batteries1. Press with a finger and slide th

Página 19 - 10 List of Functions

Instruction SiENBE12-627106 System ConfigurationATTENTION"To operate the remote control• To use the remote control, aim the transmitter at the in

Página 20 - List of Functions 11

SiENBE12-627 InstructionSystem Configuration 107NOTE"To set the clock1. Press “CLOCK button”.0:00 is displayed. blinks.2. Press “TIMER setting bu

Página 21 - 12 List of Functions

Instruction SiENBE12-627108 System Configuration2.5 Auto Dry Cool Heat Fan OperationThe air conditioner operates with the operation mode of your choic

Página 22 - Specifications

SiENBE12-627 InstructionSystem Configuration 109"To change the air flow rate setting5. Press “FAN setting button”.• Indoor unit quiet operation W

Página 23

Instruction SiENBE12-627110 System Configuration2.6 Adjusting the Air Flow DirectionFTK(X)S 20/25/35 D, ATK(X)S 20/25/35 EYou can adjust the air flow

Página 24 - 50Hz 230V

SiENBE12-627 Cooling OnlyList of Functions 3Category FunctionsFDKS25/35CAVMBFDKS25/35EAVMBCategory FunctionsFDKS25/35CAVMBFDKS25/35EAVMBBasic Function

Página 25

SiENBE12-627 InstructionSystem Configuration 111"To start COMLFORT AIRFLOW operation3. Press “COMFORT AIRFLOW button”.• The flap position will ch

Página 26

Instruction SiENBE12-627112 System ConfigurationFTK(X)S 20/25/35 C, ATK(X)S 20/25/35 DYou can adjust the air flow direction to increase your comfort.&

Página 27

SiENBE12-627 InstructionSystem Configuration 113Notes on flaps and louvers angles."To adjust the vertical blades (louvers)•Hold the knob and move

Página 28 - Duct Connected Type

Instruction SiENBE12-627114 System ConfigurationFTXG 25/35 E, ATXG 25/35 EYou can adjust the air flow direction to increase your comfort."To adju

Página 29

SiENBE12-627 InstructionSystem Configuration 115"To start COMLFORT AIRFLOW operation5. Press “COMFORT AIRFLOW button”.• The flap position will ch

Página 30

Instruction SiENBE12-627116 System ConfigurationFLK(X)S 25/35 BAdjusting the Air Flow DirectionYou can adjust the air flow direction to increase your

Página 31

SiENBE12-627 InstructionSystem Configuration 117Notes on flap and louvers angles."To adjust the vertical blades (louvers) • When adjusting the lo

Página 32

Instruction SiENBE12-627118 System Configuration.+2.7 POWERFUL OperationNOTEPOWERFUL operation quickly maximizes the cooling (heating) effect in any o

Página 33

SiENBE12-627 InstructionSystem Configuration 1192.8 OUTDOOR UNIT SILENT OperationNOTEOUTDOOR UNIT SILENT operation lowers the noise level of the outdo

Página 34

Instruction SiENBE12-627120 System Configuration2.9ECONO OperationNOTEECONO operation is a function with enables efficient operation by lowering the m

Página 35

Cooling Only SiENBE12-6274 List of FunctionsCategory FunctionsFLKS25/35BAVMB2MKS40DAVMBCategory FunctionsFLKS25/35BAVMB2MKS40DAVMBBasic FunctionInvert

Página 36

SiENBE12-627 InstructionSystem Configuration 1212.10 HOME LEAVE OperationBefore using HOME LEAVE operation.HOME LEAVE operation is a function which al

Página 37

Instruction SiENBE12-627122 System Configuration"What’s the HOME LEAVE operationIs there a set temperature and air flow rate which is most comfor

Página 38

SiENBE12-627 InstructionSystem Configuration 1232.11INTELLIGENT EYE OperationFTK(X)S 20/25/35 D, ATK(X)S 20/25/35 E“INTELLIGENT EYE” is the infrared s

Página 39

Instruction SiENBE12-627124 System Configuration“INTELLIGENT EYE” is useful for Energy SavingNotes on “INTELLIGENT EYE”CAUTION"Energy saving oper

Página 40 - 2.2 Outdoor Units

SiENBE12-627 InstructionSystem Configuration 125FTK(X)S 20/25/35 C, ATK(X)S 20/25/35 D“INTELLIGENT EYE” is the infrared sensor which detects the human

Página 41

Instruction SiENBE12-627126 System Configuration"To adjust the angle of the INTELLIGENT EYE sensor• You can adjust the angle of the INTELLIGENT E

Página 42 - Connector Wiring Diagram

SiENBE12-627 InstructionSystem Configuration 127 FTXG 25/35 E, ATXG 25/35 E“INTELLIGENT EYE” is the infrared sensor which detects the human movement.&

Página 43 - 1.1 Wall Mounted Type

Instruction SiENBE12-627128 System Configuration“INTELLIGENT EYE” is useful for Energy SavingNotes on “INTELLIGENT EYE”CAUTION"Energy saving oper

Página 44 - PCB(1): Control PCB

SiENBE12-627 InstructionSystem Configuration 1292.12 TIMER OperationNOTETimer functions are useful for automatically switching the air conditioner on

Página 45

Instruction SiENBE12-627130 System ConfigurationATTENTION"To use ON TIMER operation• Check that the clock is correct. If not, set the clock to th

Página 46 - PCB(2): Signal Receiver PCB

SiENBE12-627 Cooling OnlyList of Functions 5Category FunctionsATKS20/25/35E2V1BATKS20/25/35DAVMBCategory FunctionsATKS20/25/35E2V1BATKS20/25/35DAVMBBa

Página 47

SiENBE12-627 InstructionSystem Configuration 1312.13 Note for Multi Note<<What is a “Multi System”? >>This system has one outdoor unit con

Página 48

Instruction SiENBE12-627132 System Configuration2.14 Care and cleaningFTK(X)S 20/25/35 D, ATK(X)S 20/25/35 ECAUTIONCAUTIONBefore cleaning, be sure to

Página 49 - 1.2 Duct Connected Type

SiENBE12-627 InstructionSystem Configuration 133FILTERS1. Open the front panel.2. Pull out the air filters.• Push a little upwards the tab at the cent

Página 50 - PCB (2): Display PCB

Instruction SiENBE12-627134 System ConfigurationNOTECheck• Operation with dirty filters: (1) cannot deodorize the air. (2) cannot

Página 51

SiENBE12-627 InstructionSystem Configuration 135CAUTIONCAUTIONBefore cleaning, be sure to stop the operation and turn the breaker OFF.UNITS"Indoo

Página 52 - 5V Check

Instruction SiENBE12-627136 System ConfigurationFILTERS1. Open the front panel. 2. Pull out the air filters.• Push a little upwards the tab at the cen

Página 53 - PCB (4): Signal Receiver PCB

SiENBE12-627 InstructionSystem Configuration 137CheckNOTECheck that the base, stand and other fittings of the outdoor unit are not decayed or corroded

Página 54 - 1.4 Outdoor Unit

Instruction SiENBE12-627138 System ConfigurationCAUTIONFTXG 25/35 E, ATXG 25/35 ECAUTION• Before cleaning, be sure to stop the operation and turn the

Página 55 - PCB (2): Control PCB

SiENBE12-627 InstructionSystem Configuration 139FILTERS1. Open the front panel. • Open the front panel by placing a finger on the panel tab on either

Página 56 - Function and Control

Instruction SiENBE12-627140 System ConfigurationNOTECheck• Operation with dirty filters: (1) cannot deodorize the air. (2) cannot cl

Página 57 - 1. Main Functions

Cooling Only SiENBE12-6276 List of FunctionsCategory Functions2AMK40BAVMBCategory Functions2AMK40BAVMBBasic FunctionInverter (with Inverter Power Cont

Página 58 - Operation

SiENBE12-627 InstructionSystem Configuration 141FDK(X)S 25/35 C, FDK(X)S 25/35 ECAUTION• Only a qualified service person is allowed to perform mainten

Página 59 - Auto-Swing

Instruction SiENBE12-627142 System ConfigurationCAUTIONCheck"Cleaning the drain pan• Clean the drain pan periodically, or drain piping may be clo

Página 60 - Function and Control 51

SiENBE12-627 InstructionSystem Configuration 143CAUTIONFLK(X)S 25/35/50/60 BCAUTIONBefore cleaning, be sure to stop the operation and turn the breaker

Página 61 - Timing Chart

Instruction SiENBE12-627144 System ConfigurationFILTERS1. Open the front panel.2. Pull out the air filters.• Push upwards the tab at the center of eac

Página 62

SiENBE12-627 InstructionSystem Configuration 145CheckNOTECheck that the base, stand and other fittings of the outdoor unit are not decayed or corroded

Página 63 - 1.5 Programme Dry Function

Instruction SiENBE12-627146 System Configuration2.15 TroubleshootingThese cases are not troublesThe following cases are not air conditioner troubles b

Página 64 - 1.6 Automatic Operation

SiENBE12-627 InstructionSystem Configuration 147Check againPlease check again before calling a repair person.Case CheckThe air conditioner does not op

Página 65 - 1.7 Thermostat Control

Instruction SiENBE12-627148 System ConfigurationWARNINGIf one of the following symptoms takes place, call the service shop immediately.Disposal requir

Página 66 - 1.8 Night Set Mode

SiENBE12-627 InstructionSystem Configuration 149FAULT DIAGNOSIS BY REMOTE CONTROL.In the ARC433A series, the temperature display sections on the main

Página 67 - 1.9 ECONO Mode

Instruction SiENBE12-627150 System ConfigurationLED ON OUTDOOR UNIT PCB 3MXS, 3MKS, 4MXS, 4MKS seriesLED ON OUTDOOR UNIT PCB 2MXS, 2MKS seri

Página 68 - 1.10 INTELLIGENT EYE

SiENBE12-627 Heat PumpList of Functions 72. Heat PumpCategory FunctionsFTXG25/35EV1BW(S)FTXS20-35D3VMW(L)FTXS20-35CAVMBCategory FunctionsFTXG25/35EV1B

Página 69 - 60 Function and Control

SiENBE12-627Service Diagnosis 151Part 6Service Diagnosis1. Caution for Diagnosis...

Página 70 - 1.11 HOME LEAVE Operation

Caution for Diagnosis SiENBE12-627152 Service Diagnosis1. Caution for DiagnosisThe operation lamp flashes when any of the following errors is detected

Página 71 - Details of the

SiENBE12-627 Caution for DiagnosisService Diagnosis 153Caution: Operation stops suddenly. (Operation lamp blinks.)Cause of above trouble could be &quo

Página 72 - 1.13 Other Functions

Problem Symptoms and Measures SiENBE12-627154 Service Diagnosis2. Problem Symptoms and MeasuresSymptom Check Item Details of Measure Reference Page No

Página 73 - 1.13.10Auto-restart Function

SiENBE12-627 Service Check FunctionService Diagnosis 1553. Service Check FunctionIn the ARC433A series remote control, the temperature display section

Página 74 - 1.14 Function of Thermistor

Service Check Function SiENBE12-627156 Service DiagnosisCheck Method 2 1. Enter the diagnosis mode.Press the 3 buttons (TEMPs,TEMPt, MODE) simultaneou

Página 75 - Thermistor (DLN)

SiENBE12-627 Service Check FunctionService Diagnosis 1575. Press the TEMP button.Press TEMPs or TEMPt and change the digit until you hear the sound of

Página 76 - 1.14.2 Cooling Only Model

Troubleshooting SiENBE12-627158 Service Diagnosis4. Troubleshooting4.1 Error Codes and DescriptionH: Displayed only when system-down occurs.Code Indic

Página 77 - 2. Control Specification

SiENBE12-627 TroubleshootingService Diagnosis 1594.2 Indoor Unit PCB AbnormalityRemote control DisplayA1Method of Malfunction DetectionEvaluation of z

Página 78 - 2.2 Frequency Control

Troubleshooting SiENBE12-627160 Service Diagnosis4.3 Freeze-up Protection Control or High Pressure ControlRemote Control DisplayA5Method of Malfunctio

Página 79

Heat Pump SiENBE12-6278 List of FunctionsCategory FunctionsFDXS25/35CAVMBFDXS25/35EAVMBCategory FunctionsFDXS25/35CAVMBFDXS25/35EAVMBBasic FunctionInv

Página 80 - Function and Control 71

SiENBE12-627 TroubleshootingService Diagnosis 161TroubleshootingCheck No.06Refer to P.197NONONOCheck No. 06Indoor unit heat exchanger thermistor check

Página 81 - Frequency

Troubleshooting SiENBE12-627162 Service Diagnosis4.4 Fan Motor or Related Abnormality4.4.1 AC MotorRemote Control DisplayA6Method of Malfunction Detec

Página 82 - 2.5 Input Current Control

SiENBE12-627 TroubleshootingService Diagnosis 1634.4.2 DC MotorRemote Control DisplayA6Method of Malfunction DetectionThe rotation speed detected by t

Página 83 - 2.7 Heating Peak-cut Control

Troubleshooting SiENBE12-627164 Service DiagnosisTroubleshootingCheck No.01Refer to P.194Replace fan motor.Replace indoor unit PCB.Replace indoor unit

Página 84 - 2.8 Fan Control

SiENBE12-627 TroubleshootingService Diagnosis 1654.5 Thermistor or Related Abnormality (Indoor Unit)Remote Control DisplayC4, C9 Method of Malfunction

Página 85 - 2.10 Defrost Control

Troubleshooting SiENBE12-627166 Service Diagnosis4.6 Freeze-up Protection ControlRemote Control DisplayA5Method of Malfunction DetectionIndoor unit ic

Página 86 - Function and Control 77

SiENBE12-627 TroubleshootingService Diagnosis 167TroubleshootingCheck No.04Refer to P.194Check No.06Refer to P.197Check the wiring and piping.Check No

Página 87 - 78 Function and Control

Troubleshooting SiENBE12-627168 Service Diagnosis4.7 OL Activation (Compressor Overload)Remote Control DisplayE5Method of Malfunction DetectionA compr

Página 88 - Outline Heat Pump Only

SiENBE12-627 TroubleshootingService Diagnosis 1694.8 Compressor LockRemote Control DisplayE6Method of Malfunction DetectionA compressor lock is detect

Página 89 - 2.11.10 Oil Recovery Function

Troubleshooting SiENBE12-627170 Service Diagnosis4.9 DC Fan LockRemote Control DisplayE7Method of Malfunction DetectionA fan motor or related error is

Página 90 - 2.12 Malfunctions

SiENBE12-627 Heat PumpList of Functions 9Category FunctionsFLXS25/35BAVMB2MXS40DAVMBCategory FunctionsFLXS25/35BAVMB2MXS40DAVMBBasic FunctionInverter

Página 91 - 2.13 Forced Operation Mode

SiENBE12-627 TroubleshootingService Diagnosis 1714.10 Input Over Current DetectionRemote Control DisplayE8Method of Malfunction DetectionAn input over

Página 92 - 2.14 Additional Function

Troubleshooting SiENBE12-627172 Service DiagnosisTroubleshootingCheck No.07Refer to P.198Check No.08Refer to P.199Check No.14Refer to P.201Note: If th

Página 93 - 84 Function and Control

SiENBE12-627 TroubleshootingService Diagnosis 1734.11 Four Way Valve AbnormalityRemote Control DisplayEAMethod of Malfunction DetectionThe liquid pipe

Página 94 - System Configuration

Troubleshooting SiENBE12-627174 Service DiagnosisTroubleshootingCheck No.05Refer to P.196Check No.06Refer to P.197Check No.11Refer to P.200Correct.Rec

Página 95 - 1. System Configuration

SiENBE12-627 TroubleshootingService Diagnosis 1754.12 Discharge Pipe Temperature ControlRemote Control DisplayF3Method of Malfunction DetectionThe dis

Página 96 - Instruction

Troubleshooting SiENBE12-627176 Service Diagnosis4.13 High Pressure Control in CoolingRemote Control DisplayF6Method of Malfunction DetectionHigh-pres

Página 97 - Precautions

SiENBE12-627 TroubleshootingService Diagnosis 177TroubleshootingCheck No.04Refer to P.194Check No.06Refer to P.197Check No.07Refer to P.198Check No.09

Página 98 - System relocation

Troubleshooting SiENBE12-627178 Service Diagnosis4.14 Position Sensor AbnormalityRemote Control DisplayH6Method of Malfunction DetectionA compressor s

Página 99 - Names of Parts

SiENBE12-627 TroubleshootingService Diagnosis 1794.15 CT or Related AbnormalityRemote Control DisplayH8Method of Malfunction DetectionA CT or related

Página 100 - Outdoor Unit

Troubleshooting SiENBE12-627180 Service DiagnosisTroubleshootingCheck No.12Refer to P.200Note: If the model doesn't have SPM, replace the outdoor

Página 101 - 92 System Configuration

Heat Pump SiENBE12-62710 List of FunctionsCategory FunctionsATXG25/35EV1BATXS20/25/35E2V1BATXS20/25/35DAVMBCategory FunctionsATXG25/35EV1BATXS20/25/35

Página 102 - Indoor Unit

SiENBE12-627 TroubleshootingService Diagnosis 1814.16 Thermistor or Related Abnormality (Outdoor Unit)Remote Control DisplayP4,J3,J6,J8,J9,H9Method of

Página 103

Troubleshooting SiENBE12-627182 Service DiagnosisTroubleshootingCheck No.06Refer to P.197Turn on the power again.Reconnect.Reconnect.Replace defective

Página 104 - Remote control

SiENBE12-627 TroubleshootingService Diagnosis 1834.17 Electrical Box Temperature RiseRemote Control DisplayL3Method of Malfunction DetectionAn electri

Página 105 - 96 System Configuration

Troubleshooting SiENBE12-627184 Service DiagnosisTroubleshootingCheck No.06Refer to P.197Check No.07Refer to P.198Check No.09Refer to P.199Turn off th

Página 106

SiENBE12-627 TroubleshootingService Diagnosis 1854.18 Radiation Fin Temperature RiseRemote Control DisplayL4Method of Malfunction DetectionA radiation

Página 107

Troubleshooting SiENBE12-627186 Service DiagnosisTroubleshootingCheck No.06Refer to P.197Check No.07Refer to P.198Check No.09Refer to P.199Turn off th

Página 108 - SiENBE12-627 Instruction

SiENBE12-627 TroubleshootingService Diagnosis 1874.19 Output Over Current DetectionRemote Control DisplayL5Method of Malfunction DetectionAn output ov

Página 109 - 100 System Configuration

Troubleshooting SiENBE12-627188 Service DiagnosisTroubleshootingCheck No.07Refer to P.198Check No.08Refer to P.199Check No.13Refer to P.201Note: If th

Página 110 - System Configuration 101

SiENBE12-627 TroubleshootingService Diagnosis 1894.20 Insufficient GasRemote Control DisplayU0Method of Malfunction DetectionGas shortage detection I

Página 111

Troubleshooting SiENBE12-627190 Service DiagnosisTroubleshootingCheck No.04Refer to P.194Check No.06Refer to P.197Reconnect in position.Open the stop

Página 112

SiENBE12-627Table of Contents iInverter Multi for 2 RoomsB-SeriesD-Series!Cooling OnlyOutdoor Unit Indoor Unit2MKS40DAVMB FTKS20D3VMW(L) FDKS25CAVMBFT

Página 113 - <>

SiENBE12-627 Heat PumpList of Functions 11Category Functions2AMX40BAVMBCategory Functions2AMX40BAVMBBasic FunctionInverter (with Inverter Power Contro

Página 114 - Preparation Before Operation

SiENBE12-627 TroubleshootingService Diagnosis 1914.21 Over-voltage DetectionRemote Control DisplayU2Method of Malfunction DetectionAn abnormal voltage

Página 115 - To operate the remote control

Troubleshooting SiENBE12-627192 Service Diagnosis4.22 Anti-icing Function in Other Rooms / Unspecified Voltage (between Indoor and Outdoor Units)Remot

Página 116 - HOME LEAVE

SiENBE12-627 TroubleshootingService Diagnosis 1934.23 Outdoor Unit PCB Abnormality or Signal Transmission Circuit AbnormalityRemote Control DisplayU4M

Página 117

Check SiENBE12-627194 Service Diagnosis5. Check5.1 How to Check5.1.1 Fan Motor Connector Output CheckCheck No.01 1. Check connector connection.2. Chec

Página 118

SiENBE12-627 CheckService Diagnosis 195Valve Body Condition (Symptom) Check Method / Measure(1) Valve body catches at fully opened or half opened posi

Página 119

Check SiENBE12-627196 Service Diagnosis5.1.3 Four Way Valve Performance CheckCheck No.05Turn off the power and turn it on again.Start the heating-mode

Página 120 - System Configuration 111

SiENBE12-627 CheckService Diagnosis 1975.1.4 Thermistor Resistance CheckCheck No.06 Remove the connectors of the thermistors on the PCB, and measure t

Página 121 - 112 System Configuration

Check SiENBE12-627198 Service Diagnosis5.1.5 Installation Condition CheckCheck No.07Installation condition checkNormalChange the position of the air d

Página 122 - In HEAT or FAN mode

SiENBE12-627 CheckService Diagnosis 1995.1.6 Discharge Pressure CheckCheck No.085.1.7 Outdoor Unit Fan System Check (With DC Motor)Check No.09Discharg

Página 123 - 114 System Configuration

Check SiENBE12-627200 Service Diagnosis5.1.8 Inverter Units Refrigerant System CheckCheck No.115.1.9 Capacitor Voltage CheckCheck No.12 Before this ch

Página 124 - System Configuration 115

Heat Pump SiENBE12-62712 List of Functions

Página 125 - FLK(X)S 25/35 B

SiENBE12-627 CheckService Diagnosis 2015.1.10 Power Transistor CheckCheck No.13 " Checking the power transistor! Never touch any live parts for a

Página 126 - System Configuration 117

Check SiENBE12-627202 Service Diagnosis5.1.12 Turning Speed Pulse Input on the Outdoor Unit PCB CheckCheck No.15 <Propeller fan motor>Make sure

Página 127 - 2.7 POWERFUL Operation

SiENBE12-627Removal Procedure 203Part 7 Removal Procedure1. Outdoor Unit...

Página 128

Outdoor Unit SiENBE12-627204 Removal Procedure1. Outdoor Unit1.1 Removal of the Panels / Fan MotorProcedure Warning Be sure to wait 10 minutes or more

Página 129 - ECONO Operation

SiENBE12-627 Outdoor UnitRemoval Procedure 205" Make sure that the seven claws are fit securely when reassembling.2. Remove the top panel.1Loosen

Página 130 - Operation

Outdoor Unit SiENBE12-627206 Removal Procedure3Undo the claws and pull the front panel out towards you." The front panel has four claws." It

Página 131 - Useful in these cases

SiENBE12-627 Outdoor UnitRemoval Procedure 2073Pull the fan motor lead wire away.4Release the four claws and remove the electrical box cover.5Unscrew

Página 132 - INTELLIGENT EYE Operation

Outdoor Unit SiENBE12-627208 Removal ProcedureStepProcedure Points6Remove the propeller fan." Align mark of the propeller fan with D-cut section

Página 133 - (Top View)

SiENBE12-627 Outdoor UnitRemoval Procedure 2091.2 Removal of the PCBProcedure Warning Be sure to wait 10 minutes or more after turning off all power s

Página 134 - 1. Press “SENSOR button”

Outdoor Unit SiENBE12-627210 Removal Procedure4Disconnect the relaying connector for the compressor.5Disconnect the two connectors of the reactor.6Dis

Página 135 - Moving the sensor to the left

SiENBE12-627Specifications 13Part 2Specifications1. Cooling Only...

Página 136 - FTXG 25/35 E, ATXG 25/35 E

SiENBE12-627 Outdoor UnitRemoval Procedure 2118Disconnect the harnesses.9Loosen the screw of the terminal strip board." A thermal fuse is united

Página 137

Outdoor Unit SiENBE12-627212 Removal Procedure11Lift the PCB from the heat exchanger side, and release from the two claws." Mind that not to brea

Página 138 - 2.12 TIMER

SiENBE12-627 Outdoor UnitRemoval Procedure 213StepProcedure Points14The illustration shows the layout of the PCB (parts side).15Loosen the two screws

Página 139 - (Example)

Outdoor Unit SiENBE12-627214 Removal Procedure1.3 Removal of the Electrical BoxProcedure Warning Be sure to wait 10 minutes or more after turning off

Página 140 - 2.13 Note for Multi

SiENBE12-627 Outdoor UnitRemoval Procedure 2154Disconnect all the connectors." As for the connectors, refer to the removal procedure of PCB.5Disc

Página 141 - Fit the key

Outdoor Unit SiENBE12-627216 Removal Procedure7Lift the electrical box up.8Release the wire clamp from the back side of the electrical box.9Remove the

Página 142 - Air Filter

SiENBE12-627 Outdoor UnitRemoval Procedure 2171.4 Removal of the Sound BlanketProcedure Warning Be sure to wait 10 minutes or more after turning off a

Página 143 - Before a long idle period

Outdoor Unit SiENBE12-627218 Removal Procedure3The partition plate is fixed to the bottom frame with a claw.Lift it and pull out towards you." Fi

Página 144

SiENBE12-627 Outdoor UnitRemoval Procedure 219StepProcedure Points7Remove the sound blanket (side-inner A).8Remove the sound blanket (side-inner B).9R

Página 145 - Air filter

Outdoor Unit SiENBE12-627220 Removal Procedure1.5 Removal of the ThermistorProcedure Warning Be sure to wait 10 minutes or more after turning off all

Página 146

Cooling Only SiENBE12-62714 Specifications1. Cooling Only1.1 Indoor UnitsWall Mounted Type50Hz 230V Model FTKS20D3VMW FTKS20D3VMLRated Capacity 2.0kW

Página 147

SiENBE12-627 Outdoor UnitRemoval Procedure 2211.6 Removal of the Four Way ValveProcedure Warning Be sure to wait 10 minutes or more after turning off

Página 148

Outdoor Unit SiENBE12-627222 Removal ProcedureStepProcedure PointsWarningVentilate when refrigerant leaks during the work.(If refrigerant contacts fir

Página 149

SiENBE12-627 Outdoor UnitRemoval Procedure 2231.7 Removal of the Electronic Expansion ValveProcedure Warning Be sure to wait 10 minutes or more after

Página 150 - Cleaning the air filter

Outdoor Unit SiENBE12-627224 Removal Procedure1.8 Removal of the CompressorProcedure Warning Be sure to wait 10 minutes or more after turning off all

Página 151

SiENBE12-627 Outdoor UnitRemoval Procedure 225StepProcedure Points" Before working, make sure that the refrigerant is empty in the circuit."

Página 152 - System Configuration 143

Outdoor Unit SiENBE12-627226 Removal Procedure

Página 153

SiENBE12-627Others 227Part 8Others1. Others ...2281.1 Te

Página 154

Others SiENBE12-627228 Others1. Others1.1 Test Run from the Remote ControlFor Heat pump In cooling mode, select the lowest programmable temperature; i

Página 155 - 2.15 Troubleshooting

SiENBE12-627 OthersOthers 2291.2 Jumper Settings1.2.1 When Two Units are Installed in One RoomWhen two indoor units are installed in one room, the two

Página 156 - Check again

Others SiENBE12-627230 Others1.2.3 Adjusting the Angle of the Intelligent Eye Sensor" Once installation of the indoor unit is complete, adjust th

Página 157 - Disposal requirements

SiENBE12-627 Cooling OnlySpecifications 1550Hz 230V Model FTKS35D3VMW FTKS35D3VMLRated Capacity 3.5kW Class 3.5kW ClassFront Panel Color White Silver

Página 158 - It cancels the timer setting

SiENBE12-627Appendix 231Part 9Appendix1. Piping Diagrams...2321.1 Indoo

Página 159 - 150 System Configuration

Piping Diagrams SiENBE12-627232 Appendix1. Piping Diagrams1.1 Indoor Units1.1.1 Wall Mounted TypeFTKS20/25/35D3VMW(L),ATKS20/25/35E2V1BFTKS20/25/35CAV

Página 160 - Service Diagnosis

SiENBE12-627 Piping DiagramsAppendix 2331.1.2 Duct Connected TypeFDK(X)S25/35CAVMB,FDK(X)S25/35EAVMBFTXS20/25/35CAVMB,ATXS20/25/35DAVMBFIELD PIPING(6.

Página 161 - 1. Caution for Diagnosis

Piping Diagrams SiENBE12-627234 Appendix1.1.3 Floor / Ceiling Suspended Dual TypeFLKS25/35BAVMBFLXS25/35BAVMBFIELD PIPINGFIELD PIPING(9.5CuT)(6.4CuT)R

Página 162 - Slit for

SiENBE12-627 Piping DiagramsAppendix 2351.2 Outdoor Units2MKS40DAVMB, 2AMK40BAVMB2MXS40DAVMB, 2AMX40BAVMBREFRIGERANT FLOWOUTDOOR UNITCOOLING7.9CuT7.9C

Página 163

Wiring Diagrams SiENBE12-627236 Appendix2. Wiring Diagrams2.1 Indoor Units2.1.1 Wall Mounted TypeFTK(X)20/25/35D3VMW(L), ATK(X)S20/25/35E2V1BFTK(X)S20

Página 164 - 3. Service Check Function

SiENBE12-627 Wiring DiagramsAppendix 237FTXG25/35EV1BW(S), ATXG25/35EV1B2.1.2 Duct Connected TypeFDK(X)S25/35CAVMB, FDK(X)S25/35EAVMBPCB3R1Tt°S36S36PC

Página 165 - →See 7.)

Wiring Diagrams SiENBE12-627238 Appendix2.1.3 Floor / Ceiling Suspended Dual TypeFLK(X)S25/35BAVMBLEDH1PPCB3LEDH2PPCB4S1WLEDH3PR1TS31t°S27S25S24S26S32

Página 166 - → Refer to page 158.)

SiENBE12-627 Wiring DiagramsAppendix 2392.2 Outdoor Units2MKS40DAVMB, 2AMK40BAVMB2MXS40DAVMB, 2AMX40BAVMBPCB1 PCB2S301RED1REDZ1CWYLWVYLW3UVTRM1BLUBLU5

Página 167 - 4. Troubleshooting

Wiring Diagrams SiENBE12-627240 Appendix

Página 168 - " Faulty indoor unit PCB

Cooling Only SiENBE12-62716 Specifications50Hz 230V Model FTKS35CAVMBRated Capacity 3.5kW ClassFront Panel Color WhiteAir Flow Ratesmł/min(cfm)H 7.7 (

Página 169 - 160 Service Diagnosis

SiENBE12-627Drawings & Flow Charts 241Drawings & Flow ChartsAadjusting the angle of the intelligent eye sensor ..230anti-icing function in ot

Página 170 - Troubleshooting

SiENBE12-627242 Drawings & Flow Chartsthermistor or related abnormality (outdoor unit) ...181thermistor resistance check ...

Página 171 - 4.4.1 AC Motor

SiENBE12-627Index iIndexNumerics3 minutes stand-by ...72Aa1 ...

Página 172 - 4.4.2 DC Motor

SiENBE12-627ii Indexfan motor ...204fan motor connector output check ...

Página 173

SiENBE12-627Index iiioutdoor unit silent operation ...120output over current detection ...1

Página 174 - Service Diagnosis 165

SiENBE12-627iv Indexvaristor ...34, 36, 38, 40, 42, 45voltage detection function ...

Página 175 - 166 Service Diagnosis

Daikin Europe N.V. participates in the Eurovent Certification Programme for Air Conditioners (AC), Liquid Chilling Packages (LCP) and Fan Coil Units (

Página 176

SiENBE12-627 Cooling OnlySpecifications 1750Hz 230VModel ATKS20E2V1B ATKS25E2V1BRated Capacity 2.0kW Class 2.5kW ClassFront Panel Color White WhiteAir

Página 177 - 168 Service Diagnosis

Cooling Only SiENBE12-62718 Specifications50Hz 230VModel ATKS25DAVMB ATKS35DAVMBRated Capacity 2.5kW Class 3.5kW ClassFront Panel Color White WhiteAir

Página 178 - 4.8 Compressor Lock

SiENBE12-627 Cooling OnlySpecifications 19Duct Connected Type50Hz 230VNote: 1. The operating sound is based on the rear side suction inlet and the ext

Página 179 - 4.9 DC Fan Lock

Cooling Only SiENBE12-62720 SpecificationsFloor / Ceiling Suspended Dual Type50Hz 230VModel FLKS25BAVMB FLKS35BAVMBRated Capacity 2.5kW Class 3.5kW Cl

Página 180 - Service Diagnosis 171

SiENBE12-627ii Table of Contents1. Introduction ...v1.1 Safe

Página 181

SiENBE12-627 Cooling OnlySpecifications 211.2 Outdoor Units50Hz 230V Note: 1. The data are based on the conditions shown in the table below.Model 2MKS

Página 182 - Service Diagnosis 173

Cooling Only SiENBE12-62722 Specifications50Hz 230V Note: 1. The data are based on the conditions shown in the table below.Model 2AMK40BAVMBCooling Ca

Página 183

SiENBE12-627 Heat PumpSpecifications 232. Heat Pump2.1 Indoor UnitsWall Mounted Type50Hz 230V ModelFTXG25EV1BW FTXG25EV1BSCooling Heating Cooling Heat

Página 184 - Service Diagnosis 175

Heat Pump SiENBE12-62724 Specifications50Hz 230V ModelFTXS20D3VMW FTXS20D3VMLCooling Heating Cooling HeatingRated Capacity 2.0kW Class 2.0kW ClassFron

Página 185 - 176 Service Diagnosis

SiENBE12-627 Heat PumpSpecifications 2550Hz 230V ModelFTXS35D3VMW FTXS35D3VMLCooling Heating Cooling HeatingRated Capacity 3.5kW Class 3.5kW ClassFron

Página 186

Heat Pump SiENBE12-62726 Specifications50Hz 230V ModelFTXS35CAVMBCooling HeatingRated Capacity 3.5kW ClassFront Panel Color WhiteAir Flow Ratesmł/min(

Página 187 - 178 Service Diagnosis

SiENBE12-627 Heat PumpSpecifications 2750Hz 230V ModelATXG25EV1B ATXG35EV1BCooling Heating Cooling HeatingRated Capacity 2.5kW Class 3.5kW ClassFront

Página 188 - Service Diagnosis 179

Heat Pump SiENBE12-62728 Specifications50Hz 230V ModelATXS35E2V1B ATXS20DAVMBCooling Heating Cooling HeatingRated Capacity 3.5kW Class 2.0kW ClassFron

Página 189

SiENBE12-627 Heat PumpSpecifications 29Duct Connected Type50Hz 230VNote: 1. The operating sound is based on the rear side suction inlet and the extern

Página 190 - P4,J3,J6,J8,J9,H9

Heat Pump SiENBE12-62730 SpecificationsFloor / Ceiling Suspended Dual Type50Hz 230VModelFLXS25BAVMB FLXS35BAVMBCooling Heating Cooling HeatingRated Ca

Página 191

SiENBE12-627Table of Contents iii2.11 Electronic Expansion Valve Control ...772.12 Malfunctions ..

Página 192 - Service Diagnosis 183

SiENBE12-627 Heat PumpSpecifications 312.2 Outdoor Units50Hz 230VNote: 1. The data are based on the conditions shown in the table below.Model2MXS40DAV

Página 193

Heat Pump SiENBE12-62732 Specifications50Hz 230VNote: 1. The data are based on the conditions shown in the table below.Model2AMX40BAVMBCooling Heating

Página 194 - Service Diagnosis 185

SiENBE12-627Printed Circuit Board Connector Wiring Diagram 33Part 3Printed Circuit BoardConnector Wiring Diagram1. Printed Circuit Board Connector Wir

Página 195

Printed Circuit Board Connector Wiring Diagram SiENBE12-62734 Printed Circuit Board Connector Wiring Diagram1. Printed Circuit Board Connector Wiring

Página 196 - Service Diagnosis 187

SiENBE12-627 Printed Circuit Board Connector Wiring DiagramPrinted Circuit Board Connector Wiring Diagram 35PCB Detail PCB(1): Control PCBPCB(4): INTE

Página 197

Printed Circuit Board Connector Wiring Diagram SiENBE12-62736 Printed Circuit Board Connector Wiring Diagram1.1.2 FTK(X)S 20/25/35 C, ATK(X)S 20/25/35

Página 198 - 4.20 Insufficient Gas

SiENBE12-627 Printed Circuit Board Connector Wiring DiagramPrinted Circuit Board Connector Wiring Diagram 37PCB Detail PCB(1): Control PCBPCB(2): Sign

Página 199

Printed Circuit Board Connector Wiring Diagram SiENBE12-62738 Printed Circuit Board Connector Wiring Diagram1.1.3 FTXG 25/35 E, ATXG 25/35 EConnectors

Página 200 - 4.21 Over-voltage Detection

SiENBE12-627 Printed Circuit Board Connector Wiring DiagramPrinted Circuit Board Connector Wiring Diagram 39PCB Detail PCB(1): Control PCB (indoor uni

Página 201 - 192 Service Diagnosis

Printed Circuit Board Connector Wiring Diagram SiENBE12-62740 Printed Circuit Board Connector Wiring Diagram1.2 Duct Connected TypeConnectors PCB(1) (

Página 202 - Circuit Abnormality

SiENBE12-627iv Table of Contents1935. Check ...1945.1 H

Página 203 - 5. Check

SiENBE12-627 Printed Circuit Board Connector Wiring DiagramPrinted Circuit Board Connector Wiring Diagram 41PCB Detail PCB (2): Display PCBLED 3LED 2

Página 204

Printed Circuit Board Connector Wiring Diagram SiENBE12-62742 Printed Circuit Board Connector Wiring Diagram1.3 Floor / Ceiling Suspended Dual TypeCon

Página 205 - Check No.05

SiENBE12-627 Printed Circuit Board Connector Wiring DiagramPrinted Circuit Board Connector Wiring Diagram 43PCB Detail PCB (1): Control PCBPCB Detail

Página 206

Printed Circuit Board Connector Wiring Diagram SiENBE12-62744 Printed Circuit Board Connector Wiring DiagramPCB (3): Display PCBPCB (4): Signal Receiv

Página 207 - Check No.07

SiENBE12-627 Printed Circuit Board Connector Wiring DiagramPrinted Circuit Board Connector Wiring Diagram 451.4 Outdoor UnitConnectors PCB (1) (Filter

Página 208 - Check No.09

Printed Circuit Board Connector Wiring Diagram SiENBE12-62746 Printed Circuit Board Connector Wiring DiagramPCB Detail PCB (1): Filter PCBPCB (2): Con

Página 209 - 5.1.9 Capacitor Voltage Check

SiENBE12-627Function and Control 47Part 4 Function and Control1. Main Functions...

Página 210 - 5.1.10 Power Transistor Check

Main Functions SiENBE12-62748 Function and Control1. Main FunctionsNote: See the list of functions for the functions applicable to different models.1.

Página 211 - 5.1.13 Hall IC Check

SiENBE12-627 Main FunctionsFunction and Control 49Inverter Features The inverter provides the following features:" The regulating capacity can be

Página 212 - Removal Procedure

Main Functions SiENBE12-62750 Function and Control1.2 Power-Airflow Dual Flaps, Wide Angle Louvers and Auto-SwingPower-airflow Dual FlapsThe large fla

Página 213 - Stop valve cover

SiENBE12-627 Introductionv1. Introduction1.1 Safety CautionsCautions and Warnings" Be sure to read the following safety cautions before conductin

Página 214 - Procedure Points

SiENBE12-627 Main FunctionsFunction and Control 513-D Airflow FTXG25/35E, ATXG25/35E" Alternative repetition of vertical and horizontal swing mot

Página 215 - Fan motor

Main Functions SiENBE12-62752 Function and Control1.3 Operation Starting ControlFTXG25-35E, FTXG25-35EThe system carries out the following control at

Página 216

SiENBE12-627 Main FunctionsFunction and Control 531.4 Fan Speed Control for Indoor UnitsControl Mode The airflow rate can be automatically controlled

Página 217 - Lead wire

Main Functions SiENBE12-62754 Function and Control1.5 Programme Dry FunctionProgramme dry function removes humidity while preventing the room temperat

Página 218 - (next to S80)

SiENBE12-627 Main FunctionsFunction and Control 551.6 Automatic OperationAutomatic Cooling / Heating Function (Heat Pump Only)When the AUTO mode is se

Página 219 - Earth terminal

Main Functions SiENBE12-62756 Function and Control1.7 Thermostat ControlThermostat control is based on the difference between the room temperature and

Página 220

SiENBE12-627 Main FunctionsFunction and Control 571.8 Night Set ModeWhen the OFF timer is set, the Night Set circuit automatically activates.The Night

Página 221 - SH condenser lead wire (grey)

Main Functions SiENBE12-62758 Function and Control1.9 ECONO ModeOutline FTK(X)S20-35DThe "ECONO mode" reduces the maximum operating current

Página 222 - SH condenser

SiENBE12-627 Main FunctionsFunction and Control 591.10 INTELLIGENT EYEThis is the function that detects existence of humans in the room by a human mot

Página 223

Main Functions SiENBE12-62760 Function and Control" Since the set temperature is shifted by 2°C higher for 40 minutes, compressor speed becomes l

Página 224

Introduction SiENBE12-627vi1.1.2 Cautions Regarding Products after RepairDo not repair the electrical components with wet hands.Working on the equipme

Página 225

SiENBE12-627 Main FunctionsFunction and Control 611.11 HOME LEAVE OperationOutline In order to respond to the customer's need for immediate heati

Página 226 - Removal Procedure 217

Main Functions SiENBE12-62762 Function and Control1.12 Inverter POWERFUL OperationOutline In order to exploit the cooling and heating capacity to full

Página 227

SiENBE12-627 Main FunctionsFunction and Control 631.13 Other Functions1.13.1 Hot Start FunctionHeat Pump OnlyIn order to prevent the cold air blast th

Página 228

Main Functions SiENBE12-62764 Function and Control1.13.7 Air Purifying Filter with Photocatalytic Deodorizing FunctionThis filter incorporates the ben

Página 229 - 1.5 Removal of the Thermistor

SiENBE12-627 Main FunctionsFunction and Control 651.14 Function of Thermistor1.14.1 Heat Pump ModelA Outdoor Heat Exchanger Thermistor (DCB)1. The o

Página 230

Main Functions SiENBE12-62766 Function and ControlD Indoor Heat Exchanger Thermistor (DCN)1. The indoor heat exchanger thermistors are used for cont

Página 231 - 222 Removal Procedure

SiENBE12-627 Main FunctionsFunction and Control 671.14.2 Cooling Only ModelA Outdoor Heat Exchanger Thermistor (DCB)1. The outdoor heat exchanger th

Página 232

Control Specification SiENBE12-62768 Function and Control2. Control Specification2.1 Mode HierarchyOutline There are two modes; the mode selected in u

Página 233 - 1.8 Removal of the Compressor

SiENBE12-627 Control SpecificationFunction and Control 692.2 Frequency ControlOutline Frequency that corresponds to each room’s capacity will be deter

Página 234 - Warning

Control Specification SiENBE12-62770 Function and ControlFor Cooling Only Model1. Determine command frequency$ Command frequency will be determined in

Página 235 - 226 Removal Procedure

SiENBE12-627 Introductionvii1.1.3 Inspection after RepairBe sure to use an exclusive power circuit for the equipment, and follow the technical standar

Página 236 - Others 227

SiENBE12-627 Control SpecificationFunction and Control 713. Limit of frequency variation widthWhen the difference between input current and input curr

Página 237 - 1. Others

Control Specification SiENBE12-62772 Function and Control2.3 Controls at Mode Changing / Start-up2.3.1 Preheating OperationOutline Operate the inverte

Página 238 - 1.2 Jumper Settings

SiENBE12-627 Control SpecificationFunction and Control 732.4 Discharge Pipe ControlOutline The discharge pipe temperature is used as the compressor&ap

Página 239 - Intelligent-eye

Control Specification SiENBE12-62774 Function and Control2.6 Freeze-up Protection ControlOutline During cooling operation, the signals being sent from

Página 240 - Appendix

SiENBE12-627 Control SpecificationFunction and Control 752.8 Fan ControlOutline Fan control is carried out according to the following priority.1. Fan

Página 241 - 1. Piping Diagrams

Control Specification SiENBE12-62776 Function and Control2.10 Defrost ControlOutline Heat Pump OnlyDefrosting is carried out by the cooling cycle (rev

Página 242 - 1.1.2 Duct Connected Type

SiENBE12-627 Control SpecificationFunction and Control 772.11 Electronic Expansion Valve Control Outline The following items are included in the elect

Página 243 - FLXS25/35BAVMB

Control Specification SiENBE12-62778 Function and ControlDetail The followings are the examples of control which function in each mode by the electron

Página 244 - 1.2 Outdoor Units

SiENBE12-627 Control SpecificationFunction and Control 792.11.1 Fully Closing with Power OnInitialize the electronic expansion valve when turning on t

Página 245 - 2.1 Indoor Units

Control Specification SiENBE12-62780 Function and ControlDetail Detect DisconnectionIf a 780-second timer for open control becomes over, the following

Página 246 - 2.1.2 Duct Connected Type

Introduction SiENBE12-627viii1.1.4 Using IconsIcons are used to attract the attention of the reader to specific information. The meaning of each icon

Página 247 - 3D033909E

SiENBE12-627 Control SpecificationFunction and Control 812.12 Malfunctions2.12.1 Sensor Malfunction DetectionSensor malfunction may occur either in th

Página 248 - 3D039565B

Control Specification SiENBE12-62782 Function and Control2.12.4 Preventing Indoor FreezingDuring cooling, if the heat exchanger temperature in the ope

Página 249 - 240 Appendix

SiENBE12-627 Control SpecificationFunction and Control 832.14 Additional Function2.14.1 POWERFUL Operation ModeCompressor operating frequency and outd

Página 250 - Drawings & Flow Charts

Control Specification SiENBE12-62784 Function and Control

Página 251

SiENBE12-627System Configuration 85Part 5System Configuration1. System Configuration...

Página 252

System Configuration SiENBE12-62786 System Configuration1. System ConfigurationAfter the installation and test operation of the room air conditioner h

Página 253

SiENBE12-627 InstructionSystem Configuration 872.Instruction 2.1 Manual Contents and Reference PageH1 : Illustrations are for wall mounted type FTXS20

Página 254 - Index iii

Instruction SiENBE12-62788 System Configuration2.2Safety Precautions• Keep this manual where the operator can easily find them.• Read this manual atte

Página 255

SiENBE12-627 InstructionSystem Configuration 89Installation site"To install the air conditioner in the following types of environments, consult t

Página 256 - ÉSiENBE12-627"ËÍ

Instruction SiENBE12-62790 System Configuration2.3Names of PartsFTK(X)S 20/25/35 D, ATK(X)S 20/25/35 E"Indoor Unit16 141315121345791011862ON/OFF