3
• Split Sky Air • Outdoor Units
5
• Outdoor Units • R-410A • RN-E2V1B
3 Electrical data
RN+FTN50-60E
Representative unit combination Power supply Comp. OFM IFM
Indoor unit
Outdoor unit
Hz-volts
Voltage range
MCA MFA RHz RLA W FLA W FLA
FTN50EV1B RN50E2V1B
50 - 220
Max. 50Hz 264V
Min. 50Hz 198V
20 20 67 6.4 53 0.27 43 0.1650 - 230
50 - 240
FLKS50BAVMB RN50E2V1B
50 - 220
Max. 50Hz 264V
Min. 50Hz 198V
20 20 73 7.1 53 0.27 34 0.5450 - 230
50 - 240
FVKS50BAVMB RN50E2V1B
50 - 220
Max. 50Hz 264V
Min. 50Hz 198V
20 20 74 7.0 53 0.27 14+14 0.3150 - 230
50 - 240
FTN60EV1B RN60E2V1B
50 - 220
Max. 50Hz 264V
Min. 50Hz 198V
20 20 84 8.3 53 0.32 43 0.1650 - 230
50 - 240
3D040875C
SYMBOLS
MCA : Min. Circuit Amps (A)
MFA : Max. Fuse Amps (A)
RHz : Rated operating frequency(Hz)
RLA : Rated Load Amps (A)
OFM : Outdoor Fan Motor
IFM : Indoor Fan Motor
FLA : Full Load Amps
W : Rated motor output (W)
NOTES
1. RLA is based on the following conditions:
Indoor temp.: 27°CDB/19.0°CWB
Outdoor temp. : 35°CDB
2. Maximum allowable voltage unbalance between phases is 2%
3. Select wire size based on the larger value of MCA.
4. Instead of fuse, use circuit breaker.
5. For more details concerning conditional connections, see
http://extranet.daikineurope.com, select ’’E-Data Books’’. Finally, click
on the document title of your choice.