Si38-606 Special Control
Function 51
3.3 Pump-down Residual Operation
3.3.1 Pump-down Residual Operation in Cooling Operation
Actuator Master unit operation Slave unit operation
Compressor 210 Hz + OFF + OFF OFF
Outdoor unit fan Fan control OFF
Main motorized valve (EV1) 0 pls 0 pls
Subcooling motorized valve (EV2) 0 pls 0 pls
Hot gas bypass valve (SVP) ON OFF
Oil equalization valve (SVO) ON OFF
Receiver gas charging valve (SVL) OFF OFF
Receiver gas discharging valve (SVG) ON ON
Non-operating unit gas discharging
valve (SVSG)
OFF ON
Non-operating unit liquid pipe stop
valve (SVSL)
ON ON
Ending conditions
5 min.
Pe<0.25 MPa
Td>110°C
or