Daikin Altherma HT Manual de Serviço

Consulte online ou descarregue Manual de Serviço para Aparelhos de ar condicionado "split system" Daikin Altherma HT. Daikin Altherma HT Service manual Manual do Utilizador

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir

Resumo do Conteúdo

Página 1 - Service Manual

ESIE09-08AService ManualDaikin ALTHERMA HTERSQ 011/014/016 AA V1, Y1ERRQ 011/014/016 AA V1, Y1EKHBRD 011/014/016 AA/AB/AC V1, Y1R-410A, R-134aEKHTS

Página 2

Introduction ESIE09-08Aviii1.1.3 Inspection after RepairDo not damage or modify the power cable.Damaged or modified power cable can cause an electrica

Página 3 - Table of Contents

Field Setting ESIE09-08A88 Test OperationNotes : 1. Changes made to a field setting are only stored when the pr button is pressed. Pressing the z butt

Página 4

ESIE09-08A Field SettingTest Operation 893.1.2 Setting Contents and Code No. – EKHBRD – Indoor unitEKHBRD*AAFirst codeSecond code Setting nameInstalle

Página 5 - Table of Contents iii

Field Setting ESIE09-08A90 Test Operation7 Option setup00 Optional bottom plate heater installed 0 (OFF) 0/1 — —01 Not applicable. Do not change the d

Página 6

ESIE09-08A Field SettingTest Operation 91C Leaving water temperature limits00 Set point: leaving water maximum temperature 80 37~80 1 °C01 Set point:

Página 7 - Table of Contents v

Field Setting ESIE09-08A92 Test OperationEKHBRD*AB/ACFirst codeSecond code Setting nameInstaller setting at variance with default valueDefault value

Página 8 - 1. Introduction

ESIE09-08A Field SettingTest Operation 938 Option setup00 Remote controller temperature control 1 (ON) 0/1 — —01 Backup heater kit optional setting 1

Página 9

Field Setting ESIE09-08A94 Test Operation3.1.3 Detailed Explanation of Setting Modes[0] Remote control setup [0-00] User permission levelThe remote c

Página 10 - 1.1.3 Inspection after Repair

ESIE09-08A Field SettingTest Operation 95are possible (no ON/OFF instruction). The system keeps operating.Advantage of this method is that you can sim

Página 11 - 1.1.5 Using Icons List

Field Setting ESIE09-08A96 Test OperationOperation example: Schedule timer based on ON/OFF instruction.When setback function is enabled, the setback o

Página 12 - 1.2 PREFACE

ESIE09-08A Field SettingTest Operation 97[1] Automatic storage timing for domestic water heatingIn this mode, the indoor unit will deliver hot water t

Página 13 - Part 1 - General Information

ESIE09-08A Introductionix1.1.4 Using IconsIcons are used to attract the attention of the reader to specific information. The meaning of each icon is d

Página 14 - Outdoor Units

Field Setting ESIE09-08A98 Test Operation[2] Automatic setback function Setback function provides the possibility to lower the room temperature. The s

Página 15

ESIE09-08A Field SettingTest Operation 99[3] Weather dependent set pointWhen weather dependent operation is active, the leaving water temperature is d

Página 16 - 4 General Information

Field Setting ESIE09-08A100 Test Operation[4] Disinfection functionThis mode will disinfect the domestic hot water tank by periodically heating the do

Página 17 - Part 2 - Specifications

ESIE09-08A Field SettingTest Operation 101[5] Automatic setback and disinfection set pointSee also “[4] Disinfection function” on page 101 for more in

Página 18 - 1. Specifications

Field Setting ESIE09-08A102 Test Operation[6] Option setup [6-00] Domestic hot water tank optionIf the domestic hot water tank is installed, its oper

Página 19 - Electrical Specifications

ESIE09-08A Field SettingTest Operation 103[7] Option setup [7-00] Bottom plate heater optionAn optional bottom plate heater can be installed in your

Página 20 - 1.2 Indoor Unit

Field Setting ESIE09-08A104 Test Operation[8] Option setup [8-00] Remote controller temperature control - leaving water controlWhen using the remote

Página 21 - Specifications 9

ESIE09-08A Field SettingTest Operation 105 [8-03] Quiet modeThe unit has a quiet mode functionality for which 3 levels can be selected: [8-03] = 1 l

Página 22

Field Setting ESIE09-08A106 Test Operation[9] Automatic temperature compensationIf needed, it is possible to adjust some thermistor value of the unit

Página 23 - & Functional Parts

ESIE09-08A Field SettingTest Operation 107[A] Option setup [A-01] Current limitationThe indoor unit current is limited, the outdoor unit is slave and

Página 24 - 1. Refrigerant Circuit

Introduction ESIE09-08Ax1.2 PREFACEThank you for your continued patronage of Daikin products.This is the new service manual for Daikin's Year 200

Página 25 - Refrigerant Circuit 13

Field Setting ESIE09-08A108 Test Operation[B] Domestic hot water set pointsThe reheat mode will prevent the domestic hot water from cooling down lower

Página 26

ESIE09-08A Field SettingTest Operation 109 [b-02] Status: defines whether the weather dependent domestic water heating is turned ON (1) or OFF (0).If

Página 27 - EKHBRD 011/014/016 AA(V1/Y1)

Field Setting ESIE09-08A110 Test Operation[C] Leaving water temperature limitsTo prevent misuse concerning leaving water temperatures, it is possible

Página 28 - 16 Refrigerant Circuit

ESIE09-08A Field SettingTest Operation 111[D] Domestic water heating retention timesThe heat pump can only work in either space heating operation or d

Página 29 - 2. Functional Parts Layout

Field Setting ESIE09-08A112 Test Operation[E] Service mode [E-00] Vacuum modeWhen recovering/vacuuming of the indoor unit is needed, field setting [E

Página 30 - Back view

ESIE09-08A Field SettingTest Operation 113

Página 31 - Bird’s-eye view

Field Setting ESIE09-08A114 Test Operation3.2 Field Setting from Outdoor UnitCaution Capacity Setting after changing the main outdoor PC Board (A1P) t

Página 32

ESIE09-08A Field SettingTest Operation 115Caution Capacity Setting after changing the main indoor PC Board (A1P) to spare parts PC BoardWhen you chang

Página 33 - Top view

Field Setting ESIE09-08A116 Test Operation LED’S DURING initializing: first 12 minutes after power starting Wait until initializing period is over b

Página 34

ESIE09-08A Field SettingTest Operation 117Check item selection (Set)Contents displayMonitor modePress xx times BS2 button to select settingSetting mod

Página 35 - Overview

ESIE09-08AGeneral Information 1Part 1 - General Information1. Model Names of Indoor/Outdoor Units & Tanks...

Página 36 - 2.5 EKHTS 200/260 A/AB/AC

Field Setting ESIE09-08A118 Test Operationa. “Setting mode 1”This mode is used to set and check the following items.1. Set items ················In or

Página 37 - Worm’s-eye view

ESIE09-08A Field SettingTest Operation 119The numbers in the "No." column represent the number of times to press the SET (BS2) button.Remark

Página 38 - Tank sensor

Field Setting ESIE09-08A120 Test OperationThe numbers in the "No." column represent the number of times to press the SET (BS2) button.Note :

Página 39 - Bottom view

ESIE09-08A Field SettingTest Operation 121The numbers in the "No." column represent the number of times to press the SET (BS2) button.Note :

Página 40 - 28 Refrigerant Circuit

Field Setting ESIE09-08A122 Test OperationPush the SET button and match with the LEDs No. 1 - 15, push the RETURN button, and confirm the data for eac

Página 41 - Part 4 - Electrical Circuit

ESIE09-08A Field SettingTest Operation 1233.2.1 Setting of Refrigerant Recovery ModeWhen carrying out the refrigerant collection on site, fully open t

Página 42 - EKHBRD 011/014/016 AAV1

Field Setting ESIE09-08A124 Test Operation3.2.2 Setting of Vacuuming ModeIn order to perform vacuuming operation at site, fully open the expansion val

Página 43

ESIE09-08ATroubleshooting 127Part 7 - Troubleshooting1. Symptom-based Troubleshooting ...

Página 44

ESIE09-08A128 Troubleshooting3.32 “J9” Outdoor Unit: Malfunction of Thermistor (R4T) for Subcooling Heat Ex-changer Gas Pipe1833.33 “JA” Outdoor Unit:

Página 45

ESIE09-08A Symptom-based TroubleshootingTroubleshooting 1291. Symptom-based TroubleshootingSymptom Supposed Cause Countermeasure1 The system does not

Página 46 - 2.1 Main PCB - A1P

Model Names of Indoor/Outdoor Units & Tanks ESIE09-08A2 General Information1. Model Names of Indoor/Outdoor Units & TanksIndoor UnitsOutdoor U

Página 47

Symptom-based Troubleshooting ESIE09-08A130 Troubleshooting6 The system produces sounds.<Indoor unit>Immediately after turning ON the power supp

Página 48 - 2.2 Control - PCB - A3P

ESIE09-08A Troubleshooting by Remote ControlTroubleshooting 1312. Troubleshooting by Remote Control2.1 The INSPECTION / TEST ButtonThe following modes

Página 49 - *1: Only for EKHTS

Troubleshooting by Remote Control ESIE09-08A132 Troubleshooting2.2 Self-diagnosis by Wired Remote Control Explanation If operation stops due to malfun

Página 50 - 2.3 Inverter PCB - A4P

ESIE09-08A Troubleshooting by Remote ControlTroubleshooting 1332.3 Operation of the Remote Controller’s Inspection / Test Operation ButtonInspection/t

Página 51 - Inverter PCB

Troubleshooting by Remote Control ESIE09-08A134 Troubleshooting2.4 Remote Control Service ModeHow to Enter the Service ModeService Mode Operation Meth

Página 52

ESIE09-08A Troubleshooting by Remote ControlTroubleshooting 135Remark: The malfunction code can give also an extra subcode (alternating). With this su

Página 53 - 2.4 Filter PCB - A6P

Troubleshooting by Remote Control ESIE09-08A136 Troubleshooting2.5 Remote Controller Self-Diagnosis FunctionThe remote controller switches are equippe

Página 54 - Filter PCB - A6P

ESIE09-08A Troubleshooting by Remote ControlTroubleshooting 137 : ON : OFF c: BlinkMalfunction codeOperation lamp Malfunction contents Page R

Página 55 - 2.5 QA PCB - A5P

Troubleshooting by Remote Control ESIE09-08A138 TroubleshootingMalfunction code indication by outdoor unit PC board<Selection of setting item>&l

Página 56 - 44 Refrigerant Circuit

ESIE09-08A Troubleshooting by Remote ControlTroubleshooting 139: ON : OFF c:BlinkMalfunction codeConfirmation of malfunction 1 Confirmation of

Página 57

ESIE09-08A Model Names of Indoor/Outdoor Units & TanksGeneral Information 3TankModel Name VersionEKHTS 200 AA AB ACEKHTS 260EKHTSU 200AA AB ACEKHT

Página 58 - Inverter PCB - three phase

Troubleshooting by Remote Control ESIE09-08A140 Troubleshooting<Selection of setting item><Monitor mode><Confirmation of malfunction 1&

Página 59

ESIE09-08A Troubleshooting by Remote ControlTroubleshooting 141: ON : OFF c:BlinkMalfunction codeConfirmation of malfunction 1 Confirmation of

Página 60 - 48 Refrigerant Circuit

Troubleshooting by Indication on the Remote Controller ESIE09-08A142 Troubleshooting3. Troubleshooting by Indication on the Remote Controller3.1 “A1 ”

Página 61

ESIE09-08A Troubleshooting by Indication on the Remote ControllerTroubleshooting 1433.2 “A6 ” Indoor Unit: Pump Error (M1P) or Other Water System Erro

Página 62 - Demand PCB (option PCB A8P)

Troubleshooting by Indication on the Remote Controller ESIE09-08A144 Troubleshooting3.3 “A9 ” Indoor Unit: Malfunction of Moving Part of Electronic Ex

Página 63 - Refrigerant Circuit 51

ESIE09-08A Troubleshooting by Indication on the Remote ControllerTroubleshooting 1451: Coil check method for the moving part of the electronic expans

Página 64 - 52 Refrigerant Circuit

Troubleshooting by Indication on the Remote Controller ESIE09-08A146 Troubleshooting3.4 “AE” Indoor Unit: Water Circuit ErrorRemote Control DisplayAES

Página 65 - Part 5 - Function

ESIE09-08A Troubleshooting by Indication on the Remote ControllerTroubleshooting 1473.5 “AJ ” Indoor Unit: Malfunction of Capacity Determination Devic

Página 66 - 1. Operation Mode

Troubleshooting by Indication on the Remote Controller ESIE09-08A148 Troubleshooting3.6 “C1” Indoor Unit: Failure of Transmission (Between Indoor unit

Página 67 - 2. Basic Control

ESIE09-08A Troubleshooting by Indication on the Remote ControllerTroubleshooting 149Troubleshooting1. Pull out and insert the connecter once and chec

Página 68 - 2.2 Compressor PI Control

Model Names of Indoor/Outdoor Units & Tanks ESIE09-08A4 General Information

Página 69

Troubleshooting by Indication on the Remote Controller ESIE09-08A150 Troubleshooting3.7 “C4” Indoor Unit: Malfunction of Thermistor (R3T) Liquid Therm

Página 70 - Startup Control

ESIE09-08A Troubleshooting by Indication on the Remote ControllerTroubleshooting 1513.8 “C5 ” Indoor Unit: Malfunction of Tank Thermistor (R2T)Remote

Página 71 - 3.2 Defrosting Operation

Troubleshooting by Indication on the Remote Controller ESIE09-08A152 Troubleshooting3.9 “C9 ” Indoor Unit: Return Water Thermistor (R4T)Remote Control

Página 72

ESIE09-08A Troubleshooting by Indication on the Remote ControllerTroubleshooting 1533.10 “CA ” Indoor Unit: Leaving Water Thermistor Error (R5T)Remote

Página 73 - Stopping Operation

Troubleshooting by Indication on the Remote Controller ESIE09-08A154 Troubleshooting3.11 “CJ ” Indoor Unit: Malfunction of Thermostat Sensor in Remote

Página 74 - 4. Protection Control

ESIE09-08A Troubleshooting by Indication on the Remote ControllerTroubleshooting 1553.12 “E1 ” Outdoor Unit: PC Board DefectRemote Control DisplayE1Ap

Página 75 - In heating operation [R-134a]

Troubleshooting by Indication on the Remote Controller ESIE09-08A156 Troubleshooting3.13 “E1 ” Indoor Unit: PC Board DefectRemote Control DisplayE1Sub

Página 76 - In heating operation [R-410A]

ESIE09-08A Troubleshooting by Indication on the Remote ControllerTroubleshooting 1573.14 “E3 ” Outdoor Unit: Actuation of High Pressure SwitchRemote C

Página 77

Troubleshooting by Indication on the Remote Controller ESIE09-08A158 TroubleshootingTroubleshooting: Refer to information on page 219.NOYESYESYESNONOY

Página 78 - INV compressor [R-134a]

ESIE09-08A Troubleshooting by Indication on the Remote ControllerTroubleshooting 1593.15 “E3 ” Indoor Unit: Actuation of High Pressure SwitchRemote Co

Página 79 - Inverter Protection Control

ESIE09-08ASpecifications 5Part 2 - Specifications1. Specifications...

Página 80 - 68 Function

Troubleshooting by Indication on the Remote Controller ESIE09-08A160 Troubleshooting: Refer to information on page 219.NOYESYESNONONOYESNOYESNOYESChec

Página 81 - Heating Operation Prohibition

ESIE09-08A Troubleshooting by Indication on the Remote ControllerTroubleshooting 161+5V(4)(3)(2)(1)*1: Make a comparison between the voltage of the pr

Página 82 - 6.1 Freeze Prevention

Troubleshooting by Indication on the Remote Controller ESIE09-08A162 Troubleshooting3.16 “E4 ” Outdoor Unit: Actuation of Low Pressure SensorRemote Co

Página 83

ESIE09-08A Troubleshooting by Indication on the Remote ControllerTroubleshooting 163Troubleshooting:  Refer to information on page 220.NOYE SNOYE SNO

Página 84

Troubleshooting by Indication on the Remote Controller ESIE09-08A164 Troubleshooting3.17 “E4 ” Indoor Unit: Actuation of Low Pressure SensorRemote Con

Página 85

ESIE09-08A Troubleshooting by Indication on the Remote ControllerTroubleshooting 165:  Refer to information on page 219.NOYESNOYESNOYESCHECK 2Is thes

Página 86

Troubleshooting by Indication on the Remote Controller ESIE09-08A166 Troubleshooting3.18 “E5 ” Outdoor Unit: Inverter Compressor Motor LockRemote Cont

Página 87

ESIE09-08A Troubleshooting by Indication on the Remote ControllerTroubleshooting 1673.19 “E5 ” Indoor Unit: Inverter Compressor Motor LockRemote Contr

Página 88

Troubleshooting by Indication on the Remote Controller ESIE09-08A168 Troubleshooting3.20 “E7 ” Malfunction of Outdoor Unit Fan MotorRemote Control Dis

Página 89 - Part 6 - Test Operation

ESIE09-08A Troubleshooting by Indication on the Remote ControllerTroubleshooting 169Troubleshooting:  Refer to information on page 221.Connector of f

Página 90 - 1. Test Operation

Specifications ESIE09-08A6 Specifications1. Specifications1.1 Outdoor UnitsCapacity InformationTechnical SpecificationsFor combination indoor units +

Página 91 - 1.1.2 Turn Power On

Troubleshooting by Indication on the Remote Controller ESIE09-08A170 Troubleshooting3.21 “E9 ” Outdoor Unit: Malfunction of Moving Part of Electronic

Página 92

ESIE09-08A Troubleshooting by Indication on the Remote ControllerTroubleshooting 1711: Coil check method for the moving part of the electronic expans

Página 93 - Test Operation 81

Troubleshooting by Indication on the Remote Controller ESIE09-08A172 Troubleshooting3.22 “E9 ” Indoor Unit: Malfunction of Moving Part of Electronic E

Página 94

ESIE09-08A Troubleshooting by Indication on the Remote ControllerTroubleshooting 1731: Coil check method for the moving part of the electronic expans

Página 95

Troubleshooting by Indication on the Remote Controller ESIE09-08A174 Troubleshooting3.23 “F3 ” Outdoor Unit: Abnormal Discharge Pipe TemperatureRemote

Página 96 - 1.3.3 Check Operation

ESIE09-08A Troubleshooting by Indication on the Remote ControllerTroubleshooting 1753.24 “F3 ” Indoor Unit: Abnormal Discharge Pipe TemperatureRemote

Página 97

Troubleshooting by Indication on the Remote Controller ESIE09-08A176 Troubleshooting3.25 “H9 ” Outdoor Unit: Malfunction of Thermistor (R1T) for Outdo

Página 98 - ER(S/R)Q (011/014/016) AAV1

ESIE09-08A Troubleshooting by Indication on the Remote ControllerTroubleshooting 1773.26 “J3 ” Outdoor Unit: Malfunction of Discharge Pipe Thermistor

Página 99 - 3. Field Setting

Troubleshooting by Indication on the Remote Controller ESIE09-08A178 Troubleshooting3.27 “J3 ” Indoor Unit: Malfunction of Discharge Pipe Thermistor (

Página 100 - 88 Test Operation

ESIE09-08A Troubleshooting by Indication on the Remote ControllerTroubleshooting 1793.28 “J5 ” Outdoor Unit: Malfunction of Thermistor (R3T, R5T) for

Página 101 - EKHBRD*AA

ESIE09-08A SpecificationsSpecifications 7Electrical SpecificationsSound Level (nominal)Heating Sound Power dBASee technical dataSound Pressure dBARefr

Página 102 - 90 Test Operation

Troubleshooting by Indication on the Remote Controller ESIE09-08A180 Troubleshooting3.29 “J5 ” Indoor Unit: Malfunction of Thermistor (R7T) for Liquid

Página 103 - Test Operation 91

ESIE09-08A Troubleshooting by Indication on the Remote ControllerTroubleshooting 1813.30 “J6 ” Outdoor Unit: Malfunction of Thermistor (R6T) for Outdo

Página 104 - EKHBRD*AB/AC

Troubleshooting by Indication on the Remote Controller ESIE09-08A182 Troubleshooting3.31 “J7 ” Outdoor Unit: Malfunction of Thermistor (R7T) for Outdo

Página 105 - Test Operation 93

ESIE09-08A Troubleshooting by Indication on the Remote ControllerTroubleshooting 1833.32 “J9 ” Outdoor Unit: Malfunction of Thermistor (R4T) for Subco

Página 106 - [0] Remote control setup

Troubleshooting by Indication on the Remote Controller ESIE09-08A184 Troubleshooting3.33 “JA ” Outdoor Unit: Malfunction of High Pressure SensorRemote

Página 107 - Test Operation 95

ESIE09-08A Troubleshooting by Indication on the Remote ControllerTroubleshooting 1853.34 “JA ” Indoor Unit: Malfunction of High Pressure SensorRemote

Página 108 - OFF ONON

Troubleshooting by Indication on the Remote Controller ESIE09-08A186 Troubleshooting3.35 “JC ” Outdoor Unit: Malfunction of Low Pressure SensorRemote

Página 109 - Test Operation 97

ESIE09-08A Troubleshooting by Indication on the Remote ControllerTroubleshooting 1873.36 “JC ” Indoor Unit: Malfunction of Low Pressure SensorRemote C

Página 110 - 98 Test Operation

Troubleshooting by Indication on the Remote Controller ESIE09-08A188 Troubleshooting3.37 “L1 ” Outdoor Unit: Malfunction of PC BoardRemote Control Dis

Página 111 - Test Operation 99

ESIE09-08A Troubleshooting by Indication on the Remote ControllerTroubleshooting 1893.38 “L1 ” Indoor Unit: Malfunction of PC BoardRemote Control Disp

Página 113 - Test Operation 101

Specifications ESIE09-08A8 Specifications1.2 Indoor UnitCapacity InformationTechnical SpecificationsFor combination indoor units + outdoor unitsIndoor

Página 114 - [6] Option setup

Troubleshooting by Indication on the Remote Controller ESIE09-08A190 Troubleshooting3.39 “L4 ” Outdoor Unit: Malfunction of Inverter Radiating Fin Tem

Página 115 - [7] Option setup

ESIE09-08A Troubleshooting by Indication on the Remote ControllerTroubleshooting 1913.40 “L4 ” Indoor Unit: Malfunction of Inverter Radiating Fin Temp

Página 116 - [8] Option setup

Troubleshooting by Indication on the Remote Controller ESIE09-08A192 Troubleshooting3.41 “L5 ” Outdoor Unit: Inverter Compressor Abnormal - R-410ARem

Página 117 - Test Operation 105

ESIE09-08A Troubleshooting by Indication on the Remote ControllerTroubleshooting 1933.42 “L5 ” Indoor Unit: Inverter Compressor Abnormal - R-134aRemo

Página 118 - 24°C–2°C = 22°

Troubleshooting by Indication on the Remote Controller ESIE09-08A194 Troubleshooting3.43 “L8 ” Outdoor Unit: Inverter Current AbnormalRemote Control D

Página 119 - [A] Option setup

ESIE09-08A Troubleshooting by Indication on the Remote ControllerTroubleshooting 1953.44 “L8 ” Indoor Unit: Inverter Current AbnormalRemote Control Di

Página 120 - 108 Test Operation

Troubleshooting by Indication on the Remote Controller ESIE09-08A196 Troubleshooting3.45 “L9 ” Outdoor Unit: Inverter Start up ErrorRemote Control Dis

Página 121 - [b-04] (*)

ESIE09-08A Troubleshooting by Indication on the Remote ControllerTroubleshooting 1973.46 “L9 ” Indoor Unit: Inverter Start up ErrorRemote Control Disp

Página 122 - 110 Test Operation

Troubleshooting by Indication on the Remote Controller ESIE09-08A198 Troubleshooting3.47 “LC ” Outdoor Unit: Malfunction of Transmission between Inver

Página 123 - Test Operation 111

ESIE09-08A Troubleshooting by Indication on the Remote ControllerTroubleshooting 1993.48 “LC ” Indoor Unit: Malfunction of Transmission between Invert

Página 124 - [E] Service mode

ESIE09-08A SpecificationsSpecifications 9Main componentsAA AB AC AA AB AC AA AB ACRefrigerant side heat exchangerType Plate heat exchanger Plate heat

Página 125 - Test Operation 113

Troubleshooting by Indication on the Remote Controller ESIE09-08A200 Troubleshooting3.49 “LH ” Indoor Unit: Converter ErrorRemote Control DisplayLHSub

Página 126 - 114 Test Operation

ESIE09-08A Troubleshooting by Indication on the Remote ControllerTroubleshooting 2013.50 “P1 ” Outdoor Unit: High Voltage of Capacitor in Main Inverte

Página 127 - Test Operation 115

Troubleshooting by Indication on the Remote Controller ESIE09-08A202 Troubleshooting3.51 “P1 ” Indoor Unit: High Voltage of Capacitor in Main Inverter

Página 128 -     c

ESIE09-08A Troubleshooting by Indication on the Remote ControllerTroubleshooting 2033.52 “PJ” Indoor Unit: Faulty Combination of PCBRemote Control Dis

Página 129 - Test Operation 117

Troubleshooting by Indication on the Remote Controller ESIE09-08A204 Troubleshooting3.53 “U0 ” Low Pressure Drop Due to Refrigerant Shortage or Electr

Página 130 - 118 Test Operation

ESIE09-08A Troubleshooting by Indication on the Remote ControllerTroubleshooting 205Troubleshooting2: Voltage measurement point1: Refer to “Thermist

Página 131

Troubleshooting by Indication on the Remote Controller ESIE09-08A206 Troubleshooting3.54 “U2 ” Power Supply Insufficient or Instantaneous FailureRemot

Página 132

ESIE09-08A Troubleshooting by Indication on the Remote ControllerTroubleshooting 207Troubleshooting1: Inverter’s Power Transistors Check : Refer to i

Página 133

Troubleshooting by Indication on the Remote Controller ESIE09-08A208 Troubleshooting3.55 “U2 ” Power Supply Insufficient or Instantaneous FailureRemot

Página 134 - 32 8 2

ESIE09-08A Troubleshooting by Indication on the Remote ControllerTroubleshooting 2091: Inverter’s Power Transistors Check : Refer to information on P

Página 135 - Test Operation 123

Specifications ESIE09-08A10 SpecificationsElectrical SpecificationsPower Supply Name EKHBRD(011/014/016)AA/AB/ACV1EKHBRD(011/014/016)AA/AB/ACY111 14 1

Página 136 - 124 Test Operation

Troubleshooting by Indication on the Remote Controller ESIE09-08A210 Troubleshooting3.56 “U4 ” Malfunction of Transmission between Indoor Unit and Out

Página 137 - Part 7 - Troubleshooting

ESIE09-08A Troubleshooting by Indication on the Remote ControllerTroubleshooting 211Troubleshooting : Refer to information on P221.(V3187)CautionBe

Página 138 - 128 Troubleshooting

Troubleshooting by Indication on the Remote Controller ESIE09-08A212 Troubleshooting3.57 “U4 ” Malfunction of Transmission Indoor UnitRemote Control D

Página 139 - Circuit breaker

ESIE09-08A Troubleshooting by Indication on the Remote ControllerTroubleshooting 2133.58 “U5 ” Malfunction of Transmission between Remote Control and

Página 140

Troubleshooting by Indication on the Remote Controller ESIE09-08A214 Troubleshooting3.59 “U7 ” Indoor Unit: Malfunction of Transmission Outdoor UnitRe

Página 141

ESIE09-08A Troubleshooting by Indication on the Remote ControllerTroubleshooting 2153.60 “U8 ” Malfunction of Transmission between Main and Sub Remote

Página 142

Troubleshooting by Indication on the Remote Controller ESIE09-08A216 Troubleshooting3.61 “UA ” Communication Error between Outdoor Unit and Indoor Uni

Página 143 - Operation Button

ESIE09-08A Troubleshooting by Indication on the Remote ControllerTroubleshooting 2173.62 “UF ” System is not Set yetRemote Control DisplayUFUF subcode

Página 144 - Operation Method

Troubleshooting by Indication on the Remote Controller ESIE09-08A218 Troubleshooting3.63 “UH ” Malfunction of System, Refrigerant System Address Undef

Página 145

ESIE09-08A Troubleshooting by Indication on the Remote ControllerTroubleshooting 219[CHECK 1] Check for causes of rise in high pressureReferring to th

Página 146 - Alternating code possible

ESIE09-08ARefrigerant Circuit 11Part 3 - Refrigerant Circuit & Functional Parts1. Refrigerant Circuit ...

Página 147 - : OFF c: Blink

Troubleshooting by Indication on the Remote Controller ESIE09-08A220 Troubleshooting[CHECK 2] Check for causes of drop in low pressureReferring to the

Página 148 - Abnormal IGBT

ESIE09-08A Troubleshooting by Indication on the Remote ControllerTroubleshooting 221[CHECK 3] Check for Fan Motor Connector(1) Turn the power supply o

Página 149 - Display of contents of

Troubleshooting by Indication on the Remote Controller ESIE09-08A222 Troubleshooting

Página 150 - 140 Troubleshooting

ESIE09-08AAppendix 223Part 8 - Appendix1. Piping Diagrams ...

Página 151 - : ON : OFF c:Blink

Piping Diagrams ESIE09-08A224 Appendix1. Piping Diagrams1.1 Outdoor UnitERRQ + ERSQ 011/014/016 AAV1ELECTRONIC EXPANSION VALVE (Y3E)ELECTRONIC EXPANSI

Página 152 - Controller

ESIE09-08A Piping DiagramsAppendix 225ERRQ + ERSQ 011/014/016 AAY1ELECTRONIC EXPANSION VALVE (Y3E)ELECTRONIC EXPANSION VALVE (Y1E)HEAT EXCHANGERFILTER

Página 153

Piping Diagrams ESIE09-08A226 Appendix1.2 Indoor UnitEKHBRD 011~016 AAV1/Y1FILTER FILTERFILTER FILTERFILTERDRAIN VALVEBLOW OFFSAFETY VALVEPRESSURE GAU

Página 154 - Subcode 0

ESIE09-08A Piping DiagramsAppendix 227EKHBRD 011/014/016 AB/AC(V1/Y1)

Página 155

Piping Diagrams ESIE09-08A228 AppendixLegendPart number DescriptionR3T Liquid thermistor R-410AR4T Returning water thermistorR5T Leaving water thermis

Página 156 - All indoor unit models

ESIE09-08A Piping DiagramsAppendix 2291.3 Switch Box LayoutEKHBRD 011/014/016 AA V1EKHBRD 011/014/016 AB/AC V1A7PX3MFieldwiring to X3M, A8PFieldwiring

Página 157 - Troubleshooting 147

Refrigerant Circuit ESIE09-08A12 Refrigerant Circuit1. Refrigerant Circuit1.1 Outdoor UnitERRQ - ERSQNo. in refrigerant system diagramSymbol Name Majo

Página 158 - 148 Troubleshooting

Piping Diagrams ESIE09-08A230 AppendixLegend*: included in option kitPart number DescriptionA1P Main PCBA2P User interface PCB - remote controllerA3P

Página 159 - Troubleshooting

ESIE09-08A Piping DiagramsAppendix 231EKHBRD 011/014/016 AAY1EKHBRD 011/014/016 AB/AC Y1 A7PX3MFieldwiring to X3M, A8PFieldwiring to X2M, A7PFieldwiri

Página 160 - Thermistor R-410A

Piping Diagrams ESIE09-08A232 AppendixLegend*: included in option kitPart number DescriptionA1P Main PCBA2P User interface PCB - remote controllerA3P

Página 161 - Troubleshooting 151

ESIE09-08A Wiring DiagramsAppendix 2332. Wiring Diagrams2.1 Outdoor UnitERRQ + ERSQ 011/014/016 V1outdoorLLA3PGRNE7HF7UF8UBPHX2MA2PH1P H3P H5P H7PBS1

Página 162 - 152 Troubleshooting

Wiring Diagrams ESIE09-08A234 AppendixLegendNotesA1P Printed circuit board (main) Q1DI Field earth leakage breaker (300 mA)A2P Printed circuit board (

Página 163 - Troubleshooting 153

ESIE09-08A Wiring DiagramsAppendix 235ERRQ + ERSQ 011/014/016 Y1L1L2L3 NNL3L2L1X1MZ1CN=2Z2CN=2N=2N=13N~POWER SUPPLY380-415VQ1DIL2RREACTOR TERMINAL POS

Página 164 - Is “CJ” displayed

Wiring Diagrams ESIE09-08A236 AppendixLegendNotesA1P Printed circuit board M1C Motor (compressor)A2P Printed circuit board (inv.) M1F Motor (upper fan

Página 165 - Troubleshooting 155

ESIE09-08A Wiring DiagramsAppendix 2372.2 Field Wiring Connection DiagramERRQ + ERSQ 011/014/016 A(V1)/(Y1) in combination with EKHBRD*

Página 166 - 156 Troubleshooting

Wiring Diagrams ESIE09-08A238 AppendixX2MA3PA1PA8PA11PA10PX1MR1HA10PHAPX2M X2MK1R K3R K5R K6R K7R K8RX3YK1SK2SX3A: X5A:X7A:121X1A:1234212X8A:12123 4-t

Página 167 - Troubleshooting 157

ESIE09-08A Wiring DiagramsAppendix 239POWER SUPPLY(only for benefit KWh rate power supply installation)1~50Hz 220-240 VACNormal kWh rate power supplyR

Página 168

ESIE09-08A Refrigerant CircuitRefrigerant Circuit 13ELECTRONIC EXPANSION VALVE (Y3E)ELECTRONIC EXPANSION VALVE (Y1E)HEAT EXCHANGERFILTERFILTERFILTERFI

Página 169 - Troubleshooting 159

Wiring Diagrams ESIE09-08A240 AppendixEKHBRD 011/014/016 AB/AC V1

Página 170 - Check No.1

ESIE09-08A Wiring DiagramsAppendix 241

Página 171

Wiring Diagrams ESIE09-08A242 AppendixLegendPart number DescriptionB1PH High pressure sensorB1PL Low pressure sensorBS1 - BS4 (A9P) Push buttonC1 Capa

Página 172 - 162 Troubleshooting

ESIE09-08A Wiring DiagramsAppendix 243*: included in option kit#: field supplied*: included in option kitZ1F - Z5F (A*P) Noise filterPart number Descr

Página 173

Wiring Diagrams ESIE09-08A244 AppendixEKHBRD 011/014/016 AAY1X2MA3PA1PA8PA11PA10PX1MR1HA10PHAPX2M X2MK1R K3R K5R K6R K7R K8RX3YK1SK2SX3A: X5A:X7A:121X

Página 174 - 164 Troubleshooting

ESIE09-08A Wiring DiagramsAppendix 245POWER SUPPLY(only for benefit KWh rate power supply installation)1~50Hz 220-240 VACNormal kWh rate power supplyR

Página 175 - Check No.2

Wiring Diagrams ESIE09-08A246 AppendixEKHBRD 011/014/016 AB/AC Y1

Página 176 - (0.5MPa or more)

ESIE09-08A Wiring DiagramsAppendix 247

Página 177 - Troubleshooting 167

Wiring Diagrams ESIE09-08A248 AppendixLegendPart number DescriptionB1PH High pressure sensorB1PL Low pressure sensorBS1 - BS4 (A4P) Push buttonC1 - C2

Página 178 - 168 Troubleshooting

ESIE09-08A Wiring DiagramsAppendix 249*: included in option kit#: field supplied*: included in option kitPart number DescriptionA1P Main PCBA2P User i

Página 179

Refrigerant Circuit ESIE09-08A14 Refrigerant Circuit1.2 Indoor UnitEKHBRD 011/014/016 AA/AB/AC(V1/Y1)No. in refrigerant system diagramSymbol Name Majo

Página 180 - Expansion Valve

Wiring Diagrams ESIE09-08A250 Appendix

Página 181

ESIE09-08A Thermistor Resistance / Temperature CharacteristicsAppendix 2513. Thermistor Resistance / Temperature CharacteristicsIndoor unit For air su

Página 182 - 172 Troubleshooting

Thermistor Resistance / Temperature Characteristics ESIE09-08A252 AppendixOutdoor Unit Thermistors for Discharge Pipe (R2T)(k)T°C 0.0 0.5 T°C 0.0 0.5

Página 183

ESIE09-08A Thermistor Resistance / Temperature CharacteristicsAppendix 253Tank Thermistor (R2T)NTC-curveT°C Resistance value-20 197.81 k0 65.84 k25

Página 184 - 174 Troubleshooting

Pressure Sensor ESIE09-08A254 Appendix4. Pressure SensorLow Pressure (PL)PH = 1.38V-0.69PL = 0.57V-0.28PH : High pressure (MPa)VL : Low pressure (MPa)

Página 185 - Troubleshooting 175

ESIE09-08A Method of Replacing the Inverter’s Power Transistors ModulesAppendix 2555. Method of Replacing the Inverter’s Power Transistors ModulesWarn

Página 186 - Outdoor Air

Method of Replacing the Inverter’s Power Transistors Modules ESIE09-08A256 AppendixInverter PC boardC–C+WUV

Página 187 - Troubleshooting 177

ESIE09-08A Method of Replacing the Inverter’s Power Transistors ModulesAppendix 257Power module checkingWhen using the digital type of multiple tester

Página 188 - 178 Troubleshooting

External Backup Heater Kit ESIE09-08A258 Appendix6. External Backup Heater Kit6.1 Model NameModel NameEKBUHAA6V3EKBUHAA6W1

Página 189 - Suction Pipe 1, 2

ESIE09-08A External Backup Heater KitAppendix 2596.2 Main ComponentsBird’s-eye viewLegend6754321910811No. Name1 Water IN connection2 Heater (E*H)3 Wat

Página 190 - 180 Troubleshooting

ESIE09-08A Refrigerant CircuitRefrigerant Circuit 15EKHBRD 011/014/016 AA(V1/Y1)FILTER FILTERFILTER FILTERFILTERDRAIN VALVEBLOW OFFSAFETY VALVEPRESSUR

Página 191 - Outdoor Unit Heat Exchanger

External Backup Heater Kit ESIE09-08A260 AppendixSafety devicesCaution The heater kit air purge connection may not be used for other purposes. Therma

Página 192 - Outdoor Unit Liquid Pipe

ESIE09-08A External Backup Heater KitAppendix 2616.3 Technical SpecificationsV3 W1Heater capacityStep 1 (kW) 3 2Step 2 (kW) 6 6Dimensions H x W x D (m

Página 193 - Troubleshooting 183

External Backup Heater Kit ESIE09-08A262 Appendix6.4 Detailed Explanation of Setting ModesTo activate the heater kit some field settings on the indoor

Página 194 - 184 Troubleshooting

ESIE09-08A External Backup Heater KitAppendix 2636.5 External Backup Heater ControlNormal operationStep 0 -> Step 1& 20 minutes compressor ope

Página 195 - Troubleshooting 185

External Backup Heater Kit ESIE09-08A264 Appendix(*): approximate value (depends on operation conditions (e.g. dT, HP indoor unit))Emergency operation

Página 196 - Connect low pressure sensor

ESIE09-08A External Backup Heater KitAppendix 2656.6 Troubleshooting by Indication on the Remote ControllerRemote control displayAASubcode 0Applicable

Página 197 - Troubleshooting 187

External Backup Heater Kit ESIE09-08A266 Appendix6.7 Troubleshooting: General SymptomsGeneral heating capacity shortage (but no AA error indication)Po

Página 198 - 188 Troubleshooting

ESIE09-08A External Backup Heater KitAppendix 2676.8 Switch Box LayoutEKBUHAA6V3LegendS1LQ1LF1TF1UE1H + E2HQ2LK1MK1AK2MK5MF1B F2BX1MX2MK6MPart number

Página 199 - Troubleshooting 189

External Backup Heater Kit ESIE09-08A268 AppendixEKBUHAA6W1LegendS1LQ1LF1TF1UE1H + E2H + E3HQ2LK1MK1AK2MK5MF1BX1MX2MK2APart number DescriptionE1H, E2H

Página 200 - Temperature Rise

ESIE09-08A External Backup Heater KitAppendix 2696.9 Wiring DiagramsEKBUHAA6V3Power supplyIndoor unitOption demand PCBCommonBUH step 1 (3kW)BUH step 2

Página 201 - Temperature Rise (R8T)

Refrigerant Circuit ESIE09-08A16 Refrigerant CircuitEKHBRD 011/014/016 AB/AC(V1/Y1)

Página 202 - 192 Troubleshooting

External Backup Heater Kit ESIE09-08A270 AppendixLegend#: field suppliedNotesPart number DescriptionA8P Demand PCB (Indoor unit option)E1H, E2H Backup

Página 203 - Compressor inspection

ESIE09-08A External Backup Heater KitAppendix 271EKBUHAA6W1Power supplyIndoor unitOption demand PCBCommonBUH step 1 (2kW)BUH step 2 (6kW)

Página 204 - "L8" blinks again

External Backup Heater Kit ESIE09-08A272 AppendixLegend#: field suppliedNotesPart number DescriptionA8P Demand PCB (Indoor unit option)E1H, E2H, E3H B

Página 205 - Output current check

ESIE09-08A 3-Way ValveAppendix 2737. 3-Way Valve7.1 Build-Up of 3-Way ValveTotal assemblyLegendActuator assemblyNo. Name1 Sleeve2 Valve motor cover3 S

Página 206 - L9" blinks

3-Way Valve ESIE09-08A274 Appendix7.2 Troubleshooting Overview 3-Way ValveSymptom Possible cause CheckSpace heating circuit temperature rises when uni

Página 207 - Troubleshooting 197

ESIE09-08A 3-Way ValveAppendix 2757.3 How to Verify If 3-Way Valve is Installed CorrectlyCaution Switch off power before working on the unit but make

Página 208 - Inverter and Control PC Board

3-Way Valve ESIE09-08A276 AppendixCheck if 3-way valve motor is installed correctly on to the 3-way valve bodyCheck correct wiring and set up of the 3

Página 209

ESIE09-08A 3-Way ValveAppendix 277Check if signal towards 3-way valve is correct1. Disconnect 3-way valve wiring from terminal X2M:2-3-4. Check with a

Página 210 - 200 Troubleshooting

3-Way Valve ESIE09-08A278 Appendix

Página 211 - Have the

ESIE09-08APrecautions for New Refrigerant (R-410A) 279Part 9 - Precautions for New Refrigerant (R-410A)1. Precautions for New Refrigerant (R-410A)...

Página 212

ESIE09-08A Functional Parts LayoutRefrigerant Circuit 172. Functional Parts Layout2.1 ERRQ 011/014/016 AAV1, ERSQ 011/014/016 AAV1Bird’s-eye viewRemar

Página 213 - Troubleshooting 203

Precautions for New Refrigerant (R-410A) ESIE09-08A280 Precautions for New Refrigerant (R-410A)1. Precautions for New Refrigerant (R-410A)1.1 Outline1

Página 214 - 204 Troubleshooting

ESIE09-08A Precautions for New Refrigerant (R-410A)Precautions for New Refrigerant (R-410A) 281 Thermodynamic characteristic of R-410ATemperature(°C)

Página 215

Precautions for New Refrigerant (R-410A) ESIE09-08A282 Precautions for New Refrigerant (R-410A)1.2 Refrigerant Cylinders Cylinder specifications The

Página 216 - 206 Troubleshooting

ESIE09-08A Precautions for New Refrigerant (R-410A)Precautions for New Refrigerant (R-410A) 2831.3 Service ToolsR-410A is used under higher working pr

Página 217 - Check No.3

Precautions for New Refrigerant (R-410A) ESIE09-08A284 Precautions for New Refrigerant (R-410A)1. Flaring tool Specifications Dimension A Differenc

Página 218 - 208 Troubleshooting

ESIE09-08A Precautions for New Refrigerant (R-410A)Precautions for New Refrigerant (R-410A) 2852. Torque wrench Specifications Dimension B Unit:mmNo

Página 219

Precautions for New Refrigerant (R-410A) ESIE09-08A286 Precautions for New Refrigerant (R-410A)4. Leak tester Specifications Hydrogen detecting type

Página 220 - U4 subcode 0

ESIE09-08A Precautions for New Refrigerant (R-410A)Precautions for New Refrigerant (R-410A) 287 Differences Change in pressure Change in service po

Página 221

Precautions for New Refrigerant (R-410A) ESIE09-08A288 Precautions for New Refrigerant (R-410A)TA101A (for 10-kg cylinder) = ± 2gTA101B (for 20-kg cyl

Página 222 - AII indoor unit models

ESIE09-08AIndex iIndexAA1 ...142A6 ...

Página 223 - U5 Subcode 0

ESIE09-08ATable of Contents iTable of ContentsTable of Contents...i1. Introdu

Página 224 - 214 Troubleshooting

Functional Parts Layout ESIE09-08A18 Refrigerant CircuitBack viewR6TSubcool thermistorR3TSuction 1 thermistorR8TLiquid pipe 2 thermistorR4TCoil thermi

Página 225 - Remote Controls

ESIE09-08Aii IndexMalfunction of Tank Thermistor (R3T) ...151Malfunction of Thermistor (R3T, R5T) for Suction Pipe 1, 2 ...

Página 226 - Does the type

ESIE09-08ADrawings & Flow Charts iiiDrawings & Flow ChartsAabnormal discharge pipe temperature ...174, 175actuation of high pr

Página 227 - Troubleshooting 217

ESIE09-08Aiv Drawings & Flow ChartsTtorque wrench ...285troubleshooting by remote con

Página 228 - UH subcode 0

ESIE09-08A Functional Parts LayoutRefrigerant Circuit 192.2 ERRQ 011/014/016 AAY1, ERSQ 011/014/016 AAY1Bird’s-eye viewRemark: Bottom plate heater: S

Página 229 - Troubleshooting 219

Functional Parts Layout ESIE09-08A20 Refrigerant CircuitBack viewR3TR6TSuction thermistorR1TAmbient thermistorR8TLiquid pipe thermistorSubcool gas pip

Página 230 - 220 Troubleshooting

ESIE09-08A Functional Parts LayoutRefrigerant Circuit 212.3 EKHBRD 011/014/016 AA(V1/Y1)Front viewTop view12A34561015 14 13 12 119871619201817E

Página 231

Functional Parts Layout ESIE09-08A22 Refrigerant CircuitBird’s-eye viewLegend21222324A28272625CBD7No. Name No. Name1 High pressure sensor 18 Refrigera

Página 232 - 222 Troubleshooting

ESIE09-08A Functional Parts LayoutRefrigerant Circuit 232.4 EKHBRD 011/014/016 AB/AC(V1/Y1)OverviewLegendNo. Name No. Name1 Air purge valve 13 Manomet

Página 233 - Part 8 - Appendix

Functional Parts Layout ESIE09-08A24 Refrigerant Circuit2.5 EKHTS 200/260 A/AB/ACFront viewBottom viewTank sensorTank sensorHot water out Cold water i

Página 234 - 1. Piping Diagrams

ESIE09-08A Functional Parts LayoutRefrigerant Circuit 25Top viewWorm’s-eye viewRecirculation connectionBottom adaptorTank sensorCold water inCoil out

Página 235 - ERRQ + ERSQ 011/014/016 AAY1

Functional Parts Layout ESIE09-08A26 Refrigerant Circuit2.6 EKHTSU 200/260 A/AB/ACFront viewTank sensor

Página 236

ESIE09-08A Functional Parts LayoutRefrigerant Circuit 27Bottom viewBird’s-eye viewHot water outCold water inCoil in (from EKHBRD)Recirculation connect

Página 237 - Appendix 227

ESIE09-08Aii Table of Contents2.1 Normal Operation...552.2

Página 238

Functional Parts Layout ESIE09-08A28 Refrigerant Circuit

Página 239 - 1.3 Switch Box Layout

ESIE09-08ARefrigerant Circuit 29Part 4 - Electrical Circuit1. Switch Box Layout - Indoor Unit EKHBRD...

Página 240 - *: included in option kit

Switch Box Layout - Indoor Unit EKHBRD ESIE09-08A30 Refrigerant Circuit1. Switch Box Layout - Indoor Unit EKHBRDEKHBRD 011/014/016 AAV1EKHBRD 011/014/

Página 241 - EKHBRD 011/014/016 AB/AC Y1

ESIE09-08A Switch Box Layout - Indoor Unit EKHBRDRefrigerant Circuit 31LegendNo. Name1 Main PCB (A1P)2 Control PCB (A3P)3 Inverter PCB (A5P)4 Inverter

Página 242

Switch Box Layout - Indoor Unit EKHBRD ESIE09-08A32 Refrigerant CircuitEKHBRD 011/014/016 AB/AC V1EKHBRD 011/014/016 AB/AC Y1

Página 243 - 2. Wiring Diagrams

ESIE09-08A Switch Box Layout - Indoor Unit EKHBRDRefrigerant Circuit 33LegendNo. Name1 Main PCB (A1P)2 Control PCB (A3P)3 Inverter PCB (A5P)4 Inverter

Página 244

PCB Layout for EKHBRD 011/014/016 AA/AB/AC V1/Y1 ESIE09-08A34 Refrigerant Circuit2. PCB Layout for EKHBRD 011/014/016 AA/AB/AC V1/Y12.1 Main PCB - A1P

Página 245 - ERRQ + ERSQ 011/014/016 Y1

ESIE09-08A PCB Layout for EKHBRD 011/014/016 AA/AB/AC V1/Y1Refrigerant Circuit 35Legend*: A7P, A8P= option PCB; connection not standardConnector Conne

Página 246

PCB Layout for EKHBRD 011/014/016 AA/AB/AC V1/Y1 ESIE09-08A36 Refrigerant Circuit2.2 Control - PCB - A3PControl PCB - single phaseControl PCB - A3PX11

Página 247 - Appendix 237

ESIE09-08A PCB Layout for EKHBRD 011/014/016 AA/AB/AC V1/Y1Refrigerant Circuit 37Legend*1: Only for EKHTS*2: Only for benefit kWh rate power supply in

Página 248 - 2.3 Indoor Unit

ESIE09-08ATable of Contents iii3.7 “C4” Indoor Unit: Malfunction of Thermistor (R3T) Liquid Thermistor R-410A1503.8 “C5” Indoor Unit: Malfunction of T

Página 249 - Appendix 239

PCB Layout for EKHBRD 011/014/016 AA/AB/AC V1/Y1 ESIE09-08A38 Refrigerant Circuit2.3 Inverter PCB - A4PInverter PCB - single phasewhiteX32AredX17Ablue

Página 250 - EKHBRD 011/014/016 AB/AC V1

ESIE09-08A PCB Layout for EKHBRD 011/014/016 AA/AB/AC V1/Y1Refrigerant Circuit 39Inverter PCBLegendX106AX6AX107A X111AX9AX5AX21AX13AX11AX12AX17AX32AX2

Página 251 - Appendix 241

PCB Layout for EKHBRD 011/014/016 AA/AB/AC V1/Y1 ESIE09-08A40 Refrigerant CircuitX51A Blue - -X77A Yellow K1A & connector X3Y [9, 10] Interface re

Página 252

ESIE09-08A PCB Layout for EKHBRD 011/014/016 AA/AB/AC V1/Y1Refrigerant Circuit 412.4 Filter PCB - A6PFilter PCB - single phaseLBblueLAredearthgreen ca

Página 253 - #: field supplied

PCB Layout for EKHBRD 011/014/016 AA/AB/AC V1/Y1 ESIE09-08A42 Refrigerant CircuitFilter PCB - A6PLegendNB LBNA LA ELFNFF1UConnector Color Connected to

Página 254

ESIE09-08A PCB Layout for EKHBRD 011/014/016 AA/AB/AC V1/Y1Refrigerant Circuit 432.5 QA PCB - A5PQA PCB - single phaseQA PCB - A5PLegendwhiteX809AX801

Página 255 - Appendix 245

PCB Layout for EKHBRD 011/014/016 AA/AB/AC V1/Y1 ESIE09-08A44 Refrigerant Circuit2.6 Inverter Control PCB - Three Phase - A4PInverter control PCB - th

Página 256

ESIE09-08A PCB Layout for EKHBRD 011/014/016 AA/AB/AC V1/Y1Refrigerant Circuit 45LegendConnector Color Connected to - functionL1A - Phase L1L2A - Phas

Página 257 - Appendix 247

PCB Layout for EKHBRD 011/014/016 AA/AB/AC V1/Y1 ESIE09-08A46 Refrigerant Circuit2.7 Inverter PCB - Three Phase - A5PInverter PCB - three phaseX105AX1

Página 258

ESIE09-08A PCB Layout for EKHBRD 011/014/016 AA/AB/AC V1/Y1Refrigerant Circuit 47LegendConnector Color Connected to - functionL12A - Reactor - phase 1

Página 259

ESIE09-08Aiv Table of ContentsBoard1993.49 “LH” Indoor Unit: Converter Error ...2003.5

Página 260 - 250 Appendix

PCB Layout for EKHBRD 011/014/016 AA/AB/AC V1/Y1 ESIE09-08A48 Refrigerant Circuit2.8 Digital I/O PCB (Option PCB A7P)Digital I/O PCB (option PCB A7P)D

Página 261

ESIE09-08A PCB Layout for EKHBRD 011/014/016 AA/AB/AC V1/Y1Refrigerant Circuit 49LegendConnector Color Connected to - functionX1A White X2M [6 - 7]X2A

Página 262 - Discharge Pipe

PCB Layout for EKHBRD 011/014/016 AA/AB/AC V1/Y1 ESIE09-08A50 Refrigerant Circuit2.9 Demand PCB (Option PCB A8P)Demand PCB (option PCB A8P)Demand PCB

Página 263 - NTC-curve

ESIE09-08A PCB Layout for EKHBRD 011/014/016 AA/AB/AC V1/Y1Refrigerant Circuit 51

Página 264 - 4. Pressure Sensor

PCB Layout for EKHBRD 011/014/016 AA/AB/AC V1/Y1 ESIE09-08A52 Refrigerant Circuit

Página 265 - Appendix 255

ESIE09-08AFunction 53Part 5 - Function1. Operation Mode ...

Página 266 - Inverter PC board

Operation Mode ESIE09-08A54 Function1. Operation ModeStartup control•YesNoNoMalfunction/StandbyNormal operation••• Protection control• Pump PI control

Página 267 - Appendix 257

ESIE09-08A Basic ControlFunction 552. Basic Control2.1 Normal Operation Heating Operation Outdoor UnitHeating operation is not functional at an outd

Página 268 - 6. External Backup Heater Kit

Basic Control ESIE09-08A56 Function2.2 Compressor PI ControlCompressor PI ControlCarries out the compressor capacity PI control to maintain Tc at cons

Página 269 - 6.2 Main Components

ESIE09-08A Basic ControlFunction 572.3 Electronic Expansion Valve PI Control R-410A circuitMain Electronic Expansion Valve EV1 Control - Outdoor UnitC

Página 270 - Safety devices

ESIE09-08ATable of Contents v1.3 Service Tools ...283

Página 271 - 6.3 Technical Specifications

Special Control ESIE09-08A58 Function3. Special Control3.1 Startup ControlThis control is used to equalize the pressure in the front and back of the c

Página 272 - Detailed

ESIE09-08A Special ControlFunction 593.2 Defrosting OperationThe defrost operation is performed to solve frost on the outdoor unit heat exchanger when

Página 273 - Normal operation

Special Control ESIE09-08A60 Function3.3 Pump-down Residual OperationWhen activating compressor, if the liquid refrigerant remains in the heat-exchang

Página 274 - 264 Appendix

ESIE09-08A Special ControlFunction 613.4 Stopping OperationOperation of the actuator when the system is down, is cleared up.3.4.1 When System is in St

Página 275

Protection Control ESIE09-08A62 Function4. Protection Control4.1 High Pressure Protection ControlThis high pressure protection control is used to prev

Página 276 - (but no AA error

ESIE09-08A Protection ControlFunction 63In heating operation [R-134a]Pc>2.85MPaAfter 10 sec.Pc<2.75MPaPc>3.2MPaKeep the current stepAfter 60

Página 277 - 6.8 Switch Box Layout

Protection Control ESIE09-08A64 Function4.2 Low Pressure Protection ControlThis low pressure protection control is used to protect compressors against

Página 278 - EKBUHAA6W1

ESIE09-08A Protection ControlFunction 65In heating operation [R-134a]Pe>0.23MPaMax INV freq = max RPS for each HPandAfter 10 sec.After 10 sec.Pe<

Página 279 - 6.9 Wiring Diagrams

Protection Control ESIE09-08A66 Function4.3 Discharge Pipe Protection ControlThis discharge pipe protection control is used to protect the compressor

Página 280

ESIE09-08A Protection ControlFunction 674.4 Inverter Protection ControlInverter current protection control and inverter fin temperature control are pe

Página 281

Introduction ESIE09-08Avi1. Introduction1.1 Safety CautionsCautions and Warnings Be sure to read the following safety cautions before conducting repa

Página 282

Protection Control ESIE09-08A68 FunctionInverter fin temperature control [R-410A]Inverter fin temperature control [R-134a]Not limitedLimitedTfin ⱖ 79°

Página 283 - 7. 3-Way Valve

ESIE09-08A Other ControlFunction 695. Other Control5.1 Heating Operation Prohibition If the ambient temperature becomes higher than (24°C + value of

Página 284

Outline of Control (Indoor Unit) ESIE09-08A70 Function6. Outline of Control (Indoor Unit)6.1 Freeze PreventionFreeze-up Prevention by Thermo Off Condi

Página 285 - Separate the 3-way

ESIE09-08A Outline of Control (Indoor Unit)Function 716.2 Simultaneous demand of space heating and domestic water heatingSpace heating operation can b

Página 286

Outline of Control (Indoor Unit) ESIE09-08A72 Function2. Storage operationWhen requesting space heating and domestic water heating (storage) at the sa

Página 287 - 230V 230V

ESIE09-08A Outline of Control (Indoor Unit)Function 73External room thermostatWhen the reheat temperature is reached, the further heat up of the domes

Página 288 - 278 Appendix

Outline of Control (Indoor Unit) ESIE09-08A74 Function2. Storage operationWhen requesting space heating and domestic water heating (storage) at the sa

Página 289 - New Refrigerant (R-410A)

ESIE09-08A Outline of Control (Indoor Unit)Function 75Remote controller room temperature controlWhen the reheat temperature is reached, the further he

Página 290 - 1.1 Outline

Outline of Control (Indoor Unit) ESIE09-08A76 Function2. Storage operationWhen requesting space heating and domestic water heating (storage) at the sa

Página 291

ESIE09-08ATest Operation 77Part 6 - Test Operation1. Test Operation...

Página 292 - 1.2 Refrigerant Cylinders

ESIE09-08A Introductionvii1.1.2 Cautions Regarding Products after RepairCautionDo not repair the electrical components with wet hands.Working on the e

Página 293 - 1.3 Service Tools

Test Operation ESIE09-08A78 Test Operation1. Test Operation1.1 Procedure and OutlineFollow the following procedure to conduct the initial test operati

Página 294 - For class-2: R-410A

ESIE09-08A Test OperationTest Operation 791.1.2 Turn Power OnTurn outdoor unit power on .Turn indoor unit power on .(V3056) Be sure to turn the power

Página 295 - 5/8 27 29 27

Test Operation ESIE09-08A80 Test Operation1.2 Air Tight Test and Vacuum Drying Air tight test: Make sure to use nitrogen gas. Do this before powerin

Página 296

ESIE09-08A Test OperationTest Operation 81enter the pipe during work).After evacuating the system for 2 hours, pressurize the system to 0.05 MPa (vacu

Página 297 - Can not be used

Test Operation ESIE09-08A82 Test Operation1.3.1 Important information regarding the refrigerant usedThis product contains fluorinated greenhouse gases

Página 298

ESIE09-08A Test OperationTest Operation 831. Determine the weight of refrigerant to be charged additionally.Piping length is the one way length of gas

Página 299

Test Operation ESIE09-08A84 Test Operation1.3.3 Check Operation During check operation, mount front panel to avoid misjudging. Check operation is ma

Página 300

ESIE09-08A Test OperationTest Operation 851.4 Operation when Power is Turned On1.4.1 When Turning On Power First TimeThe unit cannot be run for up to

Página 301 - Drawings & Flow Charts

Outdoor Unit PC Board Layout ESIE09-08A86 Test Operation2. Outdoor Unit PC Board LayoutA3PA2PA4PX2MX1MER(S/R)Q (011/014/016) AAY1ER(S/R)Q (011/014/016

Página 302

ESIE09-08A Field SettingTest Operation 873. Field Setting3.1 Field Setting from remote controlIndividual function of indoor unit can be changed from t

Comentários a estes Manuais

Sem comentários