VRV-WII
The water-cooled VRV-WII uses
water as its heat source and since
there are no limitations on water
piping length, is eminently suitable
for application to tall multi storey
or large buildings. Considerable
flexibility is available within the
refrigerant circuit since up to 120m
actual piping length and 50m* (if
the VRV-WII is above the indoor
units) in height can exist between
the VRV-WII and indoor units.
Water piping does not intrude on
the occupied spaces, so there are
no leakage problems.
p. 15
7
VRVIII
VRVIII offers an extended piping
length of 165m (190m equivalent
piping length) with a total system
piping length of 1,000m.
In case the outdoor unit is located
above the indoor unit the height
difference is 50m standard. It can
be extended to 90m*
In case the outdoor unit is located
below the indoor unit, the height
difference is 40m standard. Height
differences up to maximum 90m
are possible*.
After the first branch, the longest piping length can be a maximum of 90m provided that the difference
between the longest piping length and the shortest piping length is a maximum of 40m.
* For more information, please contact your local Daikin dealer.
Extended Piping Length
Actual piping
length 120 m
Equivalent piping
length 140 m
Actual piping length
between the VRV-WII and indoor units: 120m
(Equivalent piping length: 140m)
Water piping
Refrigerant piping
(Total piping length: 300m)
Level difference between indoor units: 15m
Level difference
between the VRV-WII
and indoor units:
50m if the VRV-WII is above
40m if the VRV-WII is below
Indoor installation
Water piping length depends on the heat source equipment
VRV-WII
* 40m if the VRV-WII is below the indoor units.
165m Actual piping length *1
50m (90m*) Level difference between indoor and outdoor units
15m Level difference between indoor units
90m maximum
Actual piping
length 165 m
Equivalent piping
length 190 m
1602UKEPCEN07-200-artwork.indd 151602UKEPCEN07-200-artwork.indd 15 1/8/07 07:13:281/8/07 07:13:28