VRV-WII
The adoption of a new water heat exchanger and optimization of the
refrigerant control circuit has resulted in the industry’s most compact and
lightweight design. The unit weight of 150kg and height of 1,000mm
makes installation easy. Stacked configuration is also possible, contributing
further to space savings.
Ceiling height
Floor level
100-300mm
3,200mm
or higher
Stacked configuration is possible.
Stacked configuration
Step 1 50dB
14.7 19.9 19.9 20.9 19.9 20.1 20.2
100% 98% 78% 69% 55% 49% 44%
Step 2 45dB
11.9 15.1 15.1 15.6 15.5 15.6 15.6
93% 74% 59% 51% 43% 38% 34%
5HP 8HP 10HP 12HP 14HP 16HP 18HP
Step 1 fixes the operating sound value at 50dBA. When the sound level of an 8HP outdoor unit is fixed at
50dBA it will operate at 98 % of its nominal capacity. Step 2 fixes the operating sound value at 45dBA. When
the sound level of the same 8HP outdoor unit is fixed at 45dBA it will operate at 74 % of its nominal capacity.
For some applications the operating sound level of the outdoor unit might be too high. VRVIII super silent
mode however, allows the sound level to be fixed in order to avoid noise pollution.
Super Silent Mode
Wide Application Range
p. 16
8
9
In the event of a compressor malfunction, the remotely controlled or field
set back-up function in the outdoor unit in question (and also between
different outdoor units) will allow emergency operation of another
compressor in order to maintain 8 hour maximum interim capacity.
Back-up Function
10