102
Troubleshooting
ii) Diagnosis of Refrigerant Circuit / Application
There might be some causes where the unit starts running but does not perform satisfactorily, i.e. insuf cient
cooling. Judgement could be made by measuring temperature difference of indoor unit’s intake and discharge
air as well as running current.
: Faulty
: Check
: Cause
............... : Remedy
Insufficient cooling
Clean the coil
Clean the filter
Change or repair the motor
Remove the obstruction
Indoor / outdoor coil dirty (clogged)
Indoor air filter dirty
Restricted
Fan motor malfunction
Obstruction at air inlet / outlet of
indoor / outdoor unit
Air
circulation
Remove or reduce heat source
Reduce number of people in the room
Close the windows / doors
Excessive heat source.
e.g. electric kettle
Room overcrowded with people
Windows / doors wide open
High cooling
load
Add refrigerant. Repair leakage if detected
Repair clogging or replace faulty components
Refrigerant short charge or
refrigerant leakage
Restriction e.g. at strainer, capillary,
filter dryer, etc.
Replace compressor
Less or no compression
(Low running current)
Refrigerant
circuit
Compressor
Satisfactory operation with temperature difference of air intake & discharge of indoor unit 8°C to 13°C. *
( * value is for reference only )
Insufficient heating
Clean the coil
Clean the filter
Change or repair the motor
Remove the obstruction
Indoor / outdoor coil dirty (clogged)
Indoor air filter dirty
Restricted
Fan motor malfunction
Obstruction at air inlet / outlet of
indoor / outdoor unit
Air
circulation
Close the windows / doors
Windows / doors wide open
High cooling
load
Add refrigerant. Repair leakage if detected
Repair clogging or replace faulty components
Refrigerant short charge or
refrigerant leakage
Restriction e.g. at strainer, capillary,
filter dryer, etc.
Replace compressor
Less or no compression
(Low running current)
Refrigerant
circuit
Compressor
Satisfactory operation with temperature difference of air intake & discharge of indoor unit 14°C to 20°C. *
( * value is for reference only )
DAIKIN_FDMRN.indb 102DAIKIN_FDMRN.indb 102 1/8/2013 8:46:17 AM1/8/2013 8:46:17 AM