Application Information
Installation Guideline
Sharp edges and coil surfaces are potential injury hazard. Avoid from contact with them.
(1) Installation of Indoor Unit
Preliminary Survey
Electrical supply and installation is to con rm to local authority’s (e.g. National Electrical Board) codes and
regulations.
Voltage supply uctuation must not exceed ± 10% of rated voltage. Electricity supply lines must be
independent of welding transformers which can cause high supply uctuation.
Ensure that the location is convenient for wiring, piping and drainage.
The indoor unit must be installed in such that free from any obstacles in path of cool air discharge and
warm air return, and must allow spreading or air throughout the room (near the centre of the room).
Clearance must be provided for the indoor unit from the wall and obstacles as shown in the gure.
Use the hanger supplied with the unit.
Ensure the support is strong enough to withstand the weight of the unit.
Use the supplied drain socket to connect the drain pipe (the drain socket is only available for
FDMRN25CXV1 / FDMQN25CXV1 to FDMRN60CXV1 / FDMQN60CXV1)
Install the unit in such a way that
the condensate water can ow
out smoothly.
The diagrams below show the screws position for duct work connection.