Application Information
(5) Additional Charge
The refrigerant charge has already charged into the outdoor unit. For the piping length of 7.5m, additional
refrigerant charge after vacuuming is not necessary.
When the piping length is more than 7.5m, please use the table below (unit in gram).
R410A – Cooling Only
Indoor
FDMRN25CXV1 FDMRN35CXV1 FDMRN50CXV1 FDMRN60CXV1 FDMRN71CXV1
Outdoor
RN25CXV1 RN35CXV1
RN50CXV1
RN50CXY1
RN60CXV1
RN60CXY1
RR71CXV1
RR71CXY1
Add. Charge, g/m 13 13 15 15 33
Indoor
FDMRN100CXV1 FDMRN125CXV1 FDMRN140CXV1
Outdoor
RR90DXV1
RR90DXY1
RR100DXV1
RR100DXY1
RR125DXY1 RR140DXY1
Add. Charge, g/m 23 26 23 32
R410A – Heatpump
Indoor
FDMQN25CXV1 FDMQN35CXV1 FDMQN50CXV1 FDMQN60CXV1 FDMQN71CXV1
Outdoor
RYN25CXV1 RYN35CXV1
RYN50CXV1
RYN50CXY1
RYN60CXV1
RYN60CXY1
RQ71CXV1
RQ71CXY1
Add. Charge, g/m 20 20 20 20 46
Indoor
FDMQN100CXV1 FDMQN125CXV1 FDMQN140CXV1
Outdoor
RQ90DXV1
RQ90DXY1
RQ100DXV1
RQ100DXY1
RQ125DXY1 RQ140DXY1
Add. Charge, g/m 33 37 33 46
The additional refrigerant charge amount recommended is a guideline for longer piping application. The
actual charge required may be different from the guideline due to different application and variation in site
conditions.